11.5.50 Behaviour at setting the blockage
Options:
If the sensor is blocked after the receipt of an ON telegram, the following parameters can be
selected:
Do not send:
■
–
The sensor sends no value during blockage.
Send current value:
■
–
The sensor sends its current value during blockage also when it has not changed.
Notice
The parameter is available only when parameter "Blocking object" is set on
"Active".
11.5.51 PI controller - Value at blockage
Options:
Fixes the status for activating the blockage.
Notice
The parameter is available only when parameter "Blocking object" is set on
"Active".
Product manual 2CKA001473B9679
Description of application and parameters
Send nothing
Send value
0...100 %
Application "CO2 sensor"
│175