11.4.13 Temperature reading — Adjustment value for internal temperature measurement (x
0.1°C)
Options:
Every installation location has different physical conditions (interior or exterior wall, lightweight
or solid wall, etc.). In order to use the actual temperature at the installation location as a
measured value for the device, a temperature measurement must be performed by an external
equalised and / or calibrated thermometer at the installation location. The difference between
the actual temperature displayed on the device and the actual temperature determined by the
external measurement device must be entered in the parameter field as an "Adjustment value".
Note
11.4.14 Temperature reading — Monitoring of temperature reading
Options:
This parameter can be used to activate monitoring of temperature reading.
11.4.15 Temperature reading — Monitoring time for temperature reading
Options:
If no temperature is read within the parameterised time period, the device switches to error
mode. It sends a telegram to the bus via the "Actual temperature error" object and sets the
operating mode and control value for error. Rather small monitoring times are prevented via the
specified setting option.
Notice
The parameter is only adjustable if the "Monitoring of temperature reading"
parameter is set on "Yes".
Product manual 2CKA001473B9679
Description of application and parameters
Setting option between 1 - 100
The calibration measurement should not be carried out immediately after the
device has been installed. The device should first adjust to the ambient
temperature before calibration is carried out. The calibration measurement
should be repeated shortly before or after the room is occupied.
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
No
Yes
Setting option between 00:05:00 – 18:12:15 (hh:mm:ss)
Application "RTC"