11.4.40 Cooling control — I-component (min.)
Options:
The I-component refers to the reset time of a control. The integral component has the effect of
moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the reset time.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil". In addition,
the "Cooling type" parameter must be set on "Free configuration".
11.4.41 Cooling control — Extended settings
Options:
This parameter enables additional functions and communication objects, e.g. "Basic stage
cooling".
Product manual 2CKA001473B9679
Description of application and parameters
Setting option between 0 - 255
No
Yes
Application "RTC"