Value For Slats Position Down (%) - ABB ClimaECO SBS/Ux.0.1 Series Product Manual

Table of Contents

Advertisement

11.7.7.7

Value for slats position down (%)

Options:
The parameter is used to set the position to which the slats of the linked blind are to open. The
associated 1-byte "Sx: slat position" communication object must hereby be connected with the
1-byte slat position object of the blind actuator.
Percentage values can be set in steps of 1%. Meaning of the percentage values:
0 % = slats completely open.
100 % = slats completely closed.
Note
The parameter can only be set if the "Blind/roller blind switchover function"
parameter is set on "Blind" and the "Object type" parameter is set on "1-byte 0-
100%.
11.7.7.8
Value for slats position down (%)
Options:
The parameter is used to set the position to which the slats of the linked blind are to close. The
associated 1-byte "Sx: slat position" communication object must hereby be connected with the
1-byte slat position object of the blind actuator.
Percentage values can be set in steps of 1%. Meaning of the percentage values:
0 % = slats completely open.
100 % = slats completely closed.
Note
The parameter can only be set if the "Blind/roller blind switchover function"
parameter is set on "Blind" and the "Object type" parameter is set on "1-byte 0-
100%.
Product manual 2CKA001473B9679
Description of application and parameters
Setting option from 0 to 100 (%)
Setting option from 0 to 100 (%)