Temperature Limiter - Temperature Limit Of Additional Cooling Stage; Temperature Limiter - Temperature Limit Of Additional Cooling Stage - Limit Temperature; Temperature Limiter - Temperature Limit Of Additional Cooling Stage - Hysteresis; Temperature Limiter - Temperature Limit Of Additional Cooling Stage - Integral Component Of The Pi Controller - ABB ClimaECO SBS/Ux.0.1 Series Product Manual

Table of Contents

Advertisement

11.4.1

Temperature limiter - Temperature limit of additional cooling stage

Options:
The parameter is used to activate or deactivate the temperature limit for the additional cooling
stage.
Notice
This parameter is only available when the "Control function" parameter is set
either on "Cooling with additional stage," or "Heating and cooling with additional
stages".
11.4.1

Temperature limiter - Temperature limit of additional cooling stage - Limit temperature

Options:
The parameter is used to set the limit temperature for the basic additional cooling stage. The
temperature limit becomes active when the input temperatures are above the limit temperature.
11.4.1

Temperature limiter - Temperature limit of additional cooling stage - Hysteresis

Options:
The parameter is used to set the hysteresis for the temperature limit of the additional cooling
stage. At an active limit the temperature limit is deactivated again when the input temperatures
are above the setpoint temperature plus hysteresis.
11.4.1
Temperature limiter - Temperature limit of additional cooling stage - Integral component
of the PI controller
Options:
The parameter is used to define the processing of the I-component of a PI controller for
temperature limiting.
If the I-component is retained, this value is the starting point for continuing the PI controller after
the termination of the temperature limit. This option is suitable for slow control systems.
If the I-component is reset, the PI controller starts after the termination of the temperature limit
with an I-component of zero. This option is suitable for fast control systems.
If no PI controller is used, this parameter is without function.
11.4.2

Fan coil settings

Product manual 2CKA001473B9679
Description of application and parameters
No
Yes
Setting option between 20 - 100°C
Setting option between 0.5 - 5 K
Keep
Reset