11.4.5

Fan coil settings for cooling

Note
This parameter is only available if the "Device function" parameter is set on
either "Single device" or "Master device" and the "Control value type" parameter
is set on "Fan coil". In addition, the "Control function" parameter must be set on
either "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
11.4.1

Fan coil settings cooling - Fan speed level values

Options:
For the calculation of the fan speed level from the control value or for the output of a percentage
value for a specific fan speed level, the fan speed level value table is used. The standard value
table is the table from the KNX specification. For a deviation the values can be specified
individually.
11.4.2
Fan coil settings for cooling — Speed level 1 to 5 up to control value (0 to 255) cooling
Options:
In this parameter, the control values of the controller are assigned to fan speed levels. This
assignment is used if the fan speed levels are transmitted together with the control values.
Note
11.4.3
Fan coil settings for cooling — Fan speed level limit cooling for eco mode
Options:
This parameter limits the fan speed level when the system is switched to eco mode.
Product manual 2CKA001473B9679
Description of application and parameters
According to standard values table
Specify individually
Setting option between 0 - 255
These level settings should be adjusted to match the settings in the fan coil
actuator.
Setting the "Control value type" to "Fan coil" in the control parameters is only
useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the
control of only one fan coil actuator each for heating and cooling is
supported.
The "Fan speed level 4 - 5 up to control value (0 - 255) cooling" parameters
are available only when the "Number of fan speed levels" is set on "5 levels".
No
Yes