12.1.131 Staircase lighting - Switch-off delay

Name
GFx: Switch-off delay
The 2-byte communication object is used to receive telegrams with the set switch-off delay. The
received values are written to the memory of the device and are retained also after a power
failure.

12.1.132 Staircase lighting - Switch-off pre-warning time

Name
GFx: Switch-off pre-warning time
The 2-byte communication object "GFx: Switch-off pre-warning time" is used to receive
telegrams with the set time for switch-off pre-warning. The received values are written to the
memory of the device and are retained also after a power failure.

12.1.133 Staircase lighting - Output

Name
GFx: Output
GFx: Output
The 1-bit communication object is used to send On and Off telegrams.
The 1-byte communication object is used to send value telegrams (percentage values).
Telegrams that are received via communication object "Input" are transferred direct to object
"Output". After expiration of the switch-off delay, the "Output" object sends an Off telegram or
value "0". The bit size of the object is specified via the "Object type/number" parameter.
Product manual 2CKA001473B9679
Object function
Input
Object function
Input
Object function
Output
Output
Communication objects
Communication objects
Data type
7.005 Time (s)
Data type
7.005 Time (s)
Data type
1.001 Switching
5.001 Percent
(0..100%)