11.6.10 Relative humidity — Control value output format
Options:
The output value when the respective threshold is exceeded or undershot is defined using this
parameter.
Notice
The parameter is available only when parameter "Controller type" is set on
"Single stage", "Two-stage" or "Three-stage".
Notice
For selection of parameter setting "PI" only the selection between "Percent" or
"Byte" is available.
11.6.11 Relative humidity controller — Send control value at switchover
Notice
The parameter is available only when parameter "Control value output format" is
set on "Switching command", "Priority" or "Scene".
Options:
At each change in status between inactive/active, the corresponding control value is sent. The
parameter must be activated for this.
Product manual 2CKA001473B9679
Description of application and parameters
Switch command
Priority
Percent
Byte
Scene
Inactive
Active
"Relative humidity" application