11.5.47 PI controller — Control value at measurement failure
Options
If the internal or external measurement malfunctions or fails, a defined switch command can be
sent through this parameter.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"PI".

11.5.48 PI controller - Blocking object

Options:
The complete function of the CO2 sensor can be blocked using this parameter and with a 1 via
the corresponding communication object. Deactivation takes place by setting a value of 0.
Notice
The parameter is available only when parameter "CO2 controller type" is set on
"PI".

11.5.49 Behaviour at removing the blockage

Options:
If the sensor is enabled again after the receipt of an OFF telegram, the following parameters
can be selected:
Do not send:
The sensor only sends its value when it has changed.
Send current value:
The sensor sends its current value also when it has not changed.
Notice
The parameter is available only when parameter "Blocking object" is set on
"Active".
Product manual 2CKA001473B9679
Description of application and parameters
End priority
OFF with priority
ON with priority
Inactive
Active
Do not send any message
Send current value
Application "CO2 sensor"
│174