12.1.26 RTC - Superimposed operating mode

Name
RTC: Override operating mode
RTC: Override operating mode
(Master/Slave)
The value for the switchover of the operating mode is received via the 1-byte communication
object. Meaning of values:
"0": Override operating mode inactive
"1": Comfort
"2": Standby
"3": Economy
"4": Building protection
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller is defined by the following communication objects: (listed
in decreasing order of priority).
"RTC: Override operating mode"
"RTC: Condensate water alarm"
"RTC: Dew point alarm"
"RTC: Window contact"
"RTC: Control On/Off"
RTC: Presence detector"
"
"RTC: Normal operating mode"
Notice
When the master/slave operation is activated, the object "RTC: Override
operating mode (master/slave)" of the master and slave device must be
connected with the group address of the sending device.
Product manual 2CKA001473B9679
Object function
Input
Input
Communication objects
Communication objects
Data type
20.102 HVAC mode
20.102 HVAC mode