12.1.24 RTC - Current setpoint

Name
RTC: Current setpoint
The communication object outputs the current setpoint temperature. The value results from the
set setpoint temperature of the current operating mode, the manual setpoint temperature
adjustment and a change in the basic setpoint temperature via the "RTC: Basic set value".

12.1.25 RTC - Normal operating mode

Name
RTC: Normal operating mode
RTC: Normal operating mode
(master)
RTC: Normal operating mode
(Slave)
The value for the switchover of the operating mode is received via the 1-byte communication
object. Meaning of values:
"1": Comfort
"2": Standby
"3": Economy
"4": Building protection
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller is defined by the following communication objects (listed
in decreasing order of priority):
"RTC: Override operating mode"
"RTC: Condensate water alarm"
"RTC: Dew point alarm"
"RTC: Window contact"
"RTC: Control On/Off"
"RTC: Presence detector"
"RTC: Normal operating mode"
Notice
When the master/slave operation is activated, the object "RTC: Normal
operating mode (master)" of the master device must be connected with object
"RTC: Normal operating mode (slave)" of the slave device.
Product manual 2CKA001473B9679
Object function
Output
Object function
On
On
On
Communication objects
Communication objects
Data type
9.001 Temperature value
Data type
20.102 HVAC mode
20.102 HVAC mode
20.102 HVAC mode