Configuring 4-20 Ma Output Channels . B64 - ABB CoreSense User Manual

Hydrogen and moisture sensor
Table of Contents

Advertisement

Configuring 4–20 mA output channels
In the CoreSense Hub, 4–20 mA outputs can be defined for up to two sensors (channels 1 and 2). Both
channels can be configured the same way. In the following procedure, channel 1 is used as an example.
To configure one channel:
1 From the Publication settings page, click o420.
On the page that appears, you can configure both channels.
2 Under Channel 1, select the output that you want from the Value drop-down menu.
From the menu, you have access to 14 output channel values.
Figure 37 Selecting a channel value unit
3 Enter the appropriate values in the 4 mA value and 20 mA value fields.
When you select a value in the Value drop-down list, default values appear in the 4 mA value and 20 mA
value fields.
4 Repeat steps 2 and 3 for the second channel, if necessary.
5 Click Apply. Values are set for the output channels that you selected.
B64 Installation Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents