Configuring 4–20 mA output channels
In the CoreSense Hub, 4–20 mA outputs can be defined for up to two sensors (channels 1 and 2). Both
channels can be configured the same way. In the following procedure, channel 1 is used as an example.
To configure one channel:
1 From the Publication settings page, click o420.
On the page that appears, you can configure both channels.
2 Under Channel 1, select the output that you want from the Value drop-down menu.
From the menu, you have access to 14 output channel values.
—
Figure 37 Selecting a channel value unit
3 Enter the appropriate values in the 4 mA value and 20 mA value fields.
When you select a value in the Value drop-down list, default values appear in the 4 mA value and 20 mA
value fields.
4 Repeat steps 2 and 3 for the second channel, if necessary.
5 Click Apply. Values are set for the output channels that you selected.
B64 Installation Guide