Parameter Descriptions
3.17.6 16-8* Fieldbus & FC Port
Parameters for reporting the bus references and control
words.
16-80 Fieldbus CTW 1
3
3
Range:
0
[0 -
*
65535 ]
16-82 Fieldbus REF 1
Range:
0
[-200 - 200 ] View the 2-byte word sent with the control
*
16-83 Fieldbus REF 2
Shows the 32-bit position reference sent in PCD 2 and PCD 3. In
parameters related to PCD 2 and PCD 3, select [1683] Fieldbus REF
2 for the fieldbus which is used by the frequency converter. The
value is in position units defined in parameter group 17-7*
Position Scaling.
Range:
0 CustomRea-
doutUnit2
*
16-84 Comm. Option STW
Range:
0
[0 - 65535 ] View the extended fieldbus communication
*
16-85 FC Port CTW 1
Range:
0
[0 -
*
65535 ]
16-86 FC Port REF 1
Range:
0
[-200 -
*
200 ]
178
VLT
Function:
View the 2-byte control word (CTW) received
from the fieldbus master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile selected in
parameter 8-10 Control Profile.
For more information, refer to the relevant
fieldbus manual.
Function:
word from the fieldbus master to set the
reference value.
For more information, refer to the relevant
fieldbus manual.
Function:
[-2147483647 -
2147483647
CustomReadoutUnit2]
Function:
option status word.
For more information, refer to the relevant
fieldbus manual.
Function:
View the 2-byte control word (CTW) received
from the fieldbus master. Interpretation of the
control word depends on the fieldbus option
installed and the control word profile selected
in parameter 8-10 Control Profile.
Function:
View the 2-byte status word (STW) sent to the
fieldbus master. Interpretation of the status word
depends on the fieldbus option installed and the
Danfoss A/S © 02/2016 All rights reserved.
®
AutomationDrive FC 301/302
16-86 FC Port REF 1
Range:
16-87 Bus Readout Alarm/Warning
Range:
0
[0 - 65535] Alarm and warning numbers in hex as showed
*
16-89 Configurable Alarm/Warning Word
Range:
0
[0 - 65535] This alarm/warning word is configured in
*
3.17.7 16-9* Diagnosis Readouts
NOTICE
When using MCT 10 Set-up Software, the readout
parameters can only be read online, that is as the actual
status. This means that the status is not stored in the
MCT 10 Set-up Software file.
16-90 Alarm Word
Range:
0
[0 - 4294967295 ] View the alarm word sent via the serial
*
16-91 Alarm Word 2
Range:
0
[0 - 4294967295] View the alarm word sent via the serial
*
16-92 Warning Word
Range:
0
[0 - 4294967295 ] View the warning word sent via the serial
*
16-93 Warning Word 2
Range:
0
[0 - 4294967295] View the warning word sent via the serial
*
16-94 Ext. Status Word
Range:
0
[0 - 4294967295] Returns the extended warning word sent
*
Function:
control word profile selected in
parameter 8-10 Control Profile.
Function:
in the alarm log. The high byte contains the
alarm, the low byte the warning. The alarm
number is the first one that occurred after the
last reset.
Function:
parameter 8-17 Configurable Alarm and
Warningword to match the actual requirements.
Function:
communication port in hex code.
Function:
communication port in hex code.
Function:
communication port in hex code.
Function:
communication port in hex code.
Function:
via the serial communication port in hex
code.
MG33ML02