Danfoss VLT AutomationDrive FC 301 Programming Manual page 235

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Troubleshooting
If the alarm/warning occurs during a power sag,
use kinetic back-up (parameter 14-10 Mains
Failure).
WARNING/ALARM 8, DC under voltage
If the DC-link voltage drops below the undervoltage limit,
the frequency converter checks for 24 V DC back-up
supply. If no 24 V DC back-up supply is connected, the
frequency converter trips after a fixed time delay. The time
delay varies with unit size.
Troubleshooting
Check that the supply voltage matches the
frequency converter voltage.
Perform an input voltage test.
Perform a soft-charge circuit test.
WARNING/ALARM 9, Inverter overload
The frequency converter has run with more than 100%
overload for too long and is about to cut out. The counter
for electronic thermal inverter protection issues a warning
at 98% and trips at 100% with an alarm. The frequency
converter cannot be reset until the counter is below 90%.
Troubleshooting
Compare the output current shown on the LCP
with the frequency converter rated current.
Compare the output current shown on the LCP
with the measured motor current.
Show the thermal frequency converter load on
the LCP and monitor the value. When running
above the frequency converter continuous
current rating, the counter increases. When
running below the frequency converter
continuous current rating, the counter decreases.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the
motor is too hot. Select whether the frequency converter
issues a warning or an alarm when the counter is >90% if
parameter 1-90 Motor Thermal Protection is set to warning
options, or whether the frequency converter trips when
the counter reaches 100% if parameter 1-90 Motor Thermal
Protection is set to trip options. The fault occurs when the
motor runs with more than 100% overload for too long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
Check that the motor current set in
parameter 1-24 Motor Current is correct.
Ensure that the motor data in parameters 1-20 to
1-25 are set correctly.
If an external fan is in use, check that it is
selected in parameter 1-91 Motor External Fan.
Running AMA in parameter 1-29 Automatic Motor
Adaptation (AMA) tunes the frequency converter
MG33ML02
Programming Guide
WARNING/ALARM 11, Motor thermistor overtemp
Check whether the thermistor is disconnected. Select
whether the frequency converter issues a warning or an
alarm in parameter 1-90 Motor Thermal Protection.
Troubleshooting
WARNING/ALARM 12, Torque limit
The torque has exceeded the value in
parameter 4-16 Torque Limit Motor Mode or the value in
parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit can change this
warning from a warning-only condition to a warning
followed by an alarm.
Troubleshooting
WARNING/ALARM 13, Over current
The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts approximately
1.5 s, then the frequency converter trips and issues an
alarm. Shock loading or quick acceleration with high-inertia
loads can cause this fault. If the acceleration during ramp-
up is quick, the fault can also appear after kinetic back-up.
If extended mechanical brake control is selected, a trip can
be reset externally.
Danfoss A/S © 02/2016 All rights reserved.
to the motor more accurately and reduces
thermal loading.
Check for motor overheating.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the
thermistor is connected correctly between either
terminal 53 or 54 (analog voltage input) and
terminal 50 (+10 V supply). Also check that the
terminal switch for 53 or 54 is set for voltage.
Check that parameter 1-93 Thermistor Source
selects terminal 53 or 54.
When using terminal 18, 19, 31, 32, or 33 (digital
inputs), check that the thermistor is connected
correctly between the digital input terminal used
(digital input PNP only) and terminal 50. Select
the terminal to use in parameter 1-93 Thermistor
Source.
If the motor torque limit is exceeded during
ramp-up, extend the ramp-up time.
If the generator torque limit is exceeded during
ramp-down, extend the ramp-down time.
If torque limit occurs while running, increase the
torque limit. Make sure that the system can
operate safely at a higher torque.
Check the application for excessive current draw
on the motor.
5
5
233

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents