Parameter Descriptions
3-52 Ramp 2 Ramp Down Time
Range:
3-55 Ramp 2 S-ramp Ratio at Accel. Start
3
3
Range:
50 %
[ 1 -
*
99 %]
3-56 Ramp 2 S-ramp Ratio at Accel. End
Range:
50 %
[ 1 -
*
99 %]
3-57 Ramp 2 S-ramp Ratio at Decel. Start
Range:
50 %
[ 1 -
*
99 %]
3-58 Ramp 2 S-ramp Ratio at Decel. End
Range:
50 %
[ 1 -
*
99 %]
3.5.6 3-6* Ramp 3
Configure ramp parameters, see 3-4* Ramp 1.
3-60 Ramp 3 Type
Option:
[0]
Linear
*
78
VLT
Function:
t
  s  x n
  RPM
dec
s
Par .  3 − 52  =  
 ref   RPM
Function:
Enter the proportion of the total ramp-up time
(parameter 3-51 Ramp 2 Ramp Up Time) in
which the acceleration torque increases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-up time
(parameter 3-51 Ramp 2 Ramp Up Time) in
which the acceleration torque decreases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down
time (parameter 3-52 Ramp 2 Ramp Down Time)
where the deceleration torque increases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down
time (parameter 3-52 Ramp 2 Ramp Down Time)
where the deceleration torque decreases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
Function:
Select the ramp type, depending on
requirements for acceleration and deceleration.
A linear ramp gives constant acceleration
during ramping. An S-ramp gives non-linear
acceleration, compensating for jerk in the
application.
Danfoss A/S © 02/2016 All rights reserved.
®
AutomationDrive FC 301/302
3-60 Ramp 3 Type
Option:
[1]
S-ramp
Const Jerk
[2]
S-ramp
Const
Time
NOTICE
If [1] S-ramp Const Jerk is selected and the reference
during ramping is changed, the ramp time may be
prolonged to realize a jerk-free movement, which may
result in a longer start or stop time.
Extra adjustment of the S-ramp ratios or switching
initiators may be necessary.
3-61 Ramp 3 Ramp up Time
Range:
Size
related
3600 s]
*
3-62 Ramp 3 Ramp down Time
Range:
Size
related
3600 s]
*
3-65 Ramp 3 S-ramp Ratio at Accel. Start
Range:
50 %
[ 1 -
*
99 %]
Function:
Accelerates with lowest possible jerk.
S-ramp based on the values set in
parameter 3-61 Ramp 3 Ramp up Time and
parameter 3-62 Ramp 3 Ramp down Time.
Function:
[ 0.01 -
Enter the ramp-up time, which is the
acceleration time from 0 RPM to the
nominal motor speed n
time such that the output current does not
exceed the current limit in
parameter 4-18 Current Limit during
ramping. The value 0.00 corresponds to
0.01 s in speed mode. See ramp-down time
in parameter 3-62 Ramp 3 Ramp down Time.
Function:
[ 0.01 -
Enter the ramp-down time, which is the
deceleration time from the nominal motor
speed n
to 0 RPM. Select a ramp-down
s
time such that no overvoltage occurs in the
inverter due to regenerative operation of the
motor, and such that the generated current
does not exceed the current limit set in
parameter 4-18 Current Limit. The value 0.00
corresponds to 0.01 s in speed mode. See
ramp-up time in parameter 3-61 Ramp 3
Ramp up Time.
t
  s  x n
  RPM
dec
s
Par .  3 − 62  =  
 ref   RPM
Function:
Enter the proportion of the total ramp-up time
(parameter 3-61 Ramp 3 Ramp up Time) in
which the acceleration torque increases. The
larger the percentage value, the greater the
jerk compensation achieved, and thus the
lower the torque jerks in the application.
. Select a ramp-up
s
MG33ML02