Parameters: 3-** Reference/Ramps - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions

3.5 Parameters: 3-** Reference/Ramps

Parameters for handling of reference, definition of
limitations, and configuration of the reaction of the
frequency converter to changes.
3.5.1 3-0* Reference Limits
3-00 Reference Range
Option:
Function:
Select the range of the reference signal and the
feedback signal. Signal values can be positive only,
or positive and negative. The minimum limit may
have a negative value, unless [1] Speed closed loop
control or [3] Process is selected in
parameter 1-00 Configuration Mode.
[0] Min -
Select the range of the reference signal and the
Max
feedback signal. Signal values can be positive only,
or positive and negative. The minimum limit may
have a negative value, unless [1] Speed closed loop
control or [3] Process is selected in
parameter 1-00 Configuration Mode.
[1] -Max -
For both positive and negative values (both
directions, relative to parameter 4-10 Motor Speed
+Max
Direction).
3-01 Reference/Feedback Unit
Option:
Function:
Select the unit to be used in process PID control
references and feedbacks. Parameter 1-00 Configu-
ration Mode must be either [3] Process or [8]
Extended PID Control.
[0]
None
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
MG33ML02
Programming Guide
3-01 Reference/Feedback Unit
Option:
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[150] lb ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[180] HP
3-02 Minimum/Offset Reference
Enter the minimum reference. The minimum reference is the
lowest value obtainable by summing all references.
Minimum reference is active only when parameter 3-00 Reference
Range is set to [0] Min.- Max.
The minimum reference unit matches:
If option [10] Synchronization is selected in parameter 1-00 Config-
uration Mode, this parameter defines the maximum speed
deviation when performing the position offset defined in
parameter 3-26 Master Offset.
Range:
Size related
Danfoss A/S © 02/2016 All rights reserved.
Function:
The configuration of parameter 1-00 Configuration Mode:
for [1] Speed closed loop, RPM; for [2] Torque, Nm.
The unit selected in parameter 3-01 Reference/Feedback
Unit.
[ -999999.999 -
*
999999.999
ReferenceFeedbackUnit]
3
3
Function:
71