Parameter Descriptions
8-57 Profidrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Profile is set to [1]
Profidrive profile.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-58 Profidrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the fieldbus. This parameter is
active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Profile is set to [1]
Profidrive profile.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
3.10.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the frequency converter port.
8-80 Bus Message Count
Range:
Function:
0
[0 - 0 ] This parameter shows the number of valid
*
telegrams detected on the bus.
8-81 Bus Error Count
Array [6]
Range:
Function:
0
[0 - 0 ] This parameter shows the number of telegrams
*
with faults (for example CRC fault) detected on the
bus.
8-82 Slave Messages Rcvd
Range:
Function:
0
[0 - 0 ] This parameter shows the number of valid
*
telegrams addressed to the slave sent by the
frequency converter.
8-83 Slave Error Count
Range:
Function:
0
[0 - 0 ] This parameter shows the number of error
*
telegrams, which could not be executed by the
frequency converter.
MG33ML02
Programming Guide
3.10.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range:
100 RPM
Function:
8-91 Bus Jog 2 Speed
Range:
200 RPM
Function:
Danfoss A/S © 02/2016 All rights reserved.
Function:
[ 0 - par. 4-13
Enter the jog speed. Activate this
*
RPM]
fixed jog speed via the serial port
or fieldbus option.
Function:
[ 0 - par. 4-13
Enter the jog speed. Activate this
*
RPM]
fixed jog speed via the serial port
or fieldbus option.
3
3
137