Parameters: 36-** Programmable I/O Option - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions
3.26 Parameters: 36-** Programmable I/O
Option
Parameters for configuring VLT
115.
3
3
Parameters in this group are active only when VLT
Programmable I/O MCB 115 is installed.
3.26.1 36-0* I/O Mode
®
VLT
Programmable I/O MCB 115 has 3 analog inputs and
3 configurable analog outputs. Use the parameters in this
group to configure the mode of the analog outputs.
Terminals can be programmed to provide voltage, current,
or digital output.
36-03 Terminal X49/7 Mode
Select the output mode of analog terminal X49/7.
Option:
[0]
*
[1]
[2]
[3]
36-04 Terminal X49/9 Mode
Select the output mode of analog terminal X49/9.
Option:
[0]
*
[1]
[2]
[3]
36-05 Terminal X49/11 Mode
Select the output mode of analog terminal X49/11.
Option:
[0]
*
[1]
[2]
[3]
3.26.2 36-4* Output X49/7
®
VLT
Programmable I/O MCB 115 has 3 analog inputs and
3 configurable analog outputs. Use the parameters in this
group to configure the mode of the analog outputs.
Select the functionality of terminal X49/7.
36-40 Terminal X49/7 Analogue Output
Option:
[0]
No operation
*
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor Current
192
®
Programmable I/O MCB
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Function:
Voltage 0-10V
Voltage 2-10V
Current 0-20mA
Current 4-20mA
Danfoss A/S © 02/2016 All rights reserved.
®
VLT
AutomationDrive FC 301/302
36-40 Terminal X49/7 Analogue Output
Option:
[104]
[105]
[106]
®
[107]
[108]
[109]
[139]
[141]
36-42 Terminal X49/7 Min. Scale
Match the minimum output of terminal X49/7 with a required
value. The required value is defined as a percentage of the value
selected in parameter 36-40 Terminal X49/7 Analogue Output. To
know more about how this parameter works, see
parameter 6-52 Terminal 42 Output Max Scale.
The following example describes how the frequency converter
uses this parameter.
Example
Parameter 36-03 Terminal X49/7 Mode=[0] Voltage 0-10 V
Parameter 36-40 Terminal X49/7 Analogue Output=[100] Output
frequency
Parameter 4-19 Max Output Frequency=200 Hz
Application requirement: If the output frequency is lower than 20
Hz, the output of terminal X49/7 should be 0 V. To fulfil the
example requirement, enter 10% in parameter 36-42 Terminal
X49/7 Min. Scale.
Range:
0 %
*
36-43 Terminal X49/7 Max. Scale
Range:
100 %
*
36-44 Terminal X49/7 Bus Control
This parameter contains the output level of terminal X49/7 if the
terminal is controlled by a fieldbus.
Range:
0 %
*
36-45 Terminal X49/7 Timeout Preset
The frequency converter sends the value of this parameter to the
output terminal when the terminal is controlled by a fieldbus
and a timeout is detected.
Range:
0 %
*
3.26.3 36-5* Output X49/9
Function:
®
VLT
Programmable I/O MCB 115 has 3 analog inputs and
3 configurable analog outputs. Use the parameters in this
group to configure the mode of the analog outputs.
Torque rel to limit
Torq relate to rated
Power
Speed
Torque
Max Out Freq
Bus ctrl. 0-20 mA
Bus ctrl 0-20mA t.o.
Function:
[0 - 200 %]
Function:
[0 - 200 %]
Function:
[0 - 100 %]
Function:
[0 - 100 %]
Function:
MG33ML02