General Specifications - Danfoss VLT AutomationDrive Design Manual

Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

FC 300 Selection

4.5 General Specifications

Mains supply:
Supply Terminals (6-Pulse)
Supply Terminals (12-Pulse)
Supply voltage
Supply voltage
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the FC continues until the intermediate circuit voltage drops below the minimum
stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up and full
torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5kW
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW
Switching on input supply L1, L2, L3 (power-ups) ≥ 90kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/
690V maximum.
Motor output (U, V, W):
Output voltage
Output frequency (0.25-75kW)
Output frequency (90-1000kW)
Output frequency in Flux Mode (FC 302 only)
Switching on output
Ramp times
1)
Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Overload torque (Variable torque)
Pulse
Pause
160%/1min
91.8%/10 min
150%/1min
93.5%/10 min
110%/1min
98.9%/10 min
Table 4.1 Overload capability
Torque rise time in VVC+ (independent of fsw)
Torque rise time in FLUX (for 5 kHz fsw)
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Cable lengths and cross sections for control cables
Max. motor cable length, screened
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
FC 300 Design Guide
Pulse
160%/60 s
150%/60 s
110%/60 s
Table 4.2 Overload capability
1)
:
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
FC 301: 380-480V / FC 302: 380-500V ±10%
FC 302: 525-600V ±10%
FC 302: 525-690V ±10%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
maximum 2 times/min.
maximum 1 time/min.
maximum 1 time/2 min.
overvoltage category III/pollution degree 2
0 - 100% of supply voltage
FC 301: 0.2 - 1000Hz / FC 302: 0 - 1000Hz
maximum 160% for 60 sec.
maximum 180% up to 0.5 sec.
maximum 160% for 60 sec.
maximum 110% for 60 sec.
maximum 110% for 60 sec.
Pause
0%/94 s
0%/75 s
0%/60 s
FC 301: 50m/FC 301 (A1): 25m/ FC 302: 150m
FC 301: 75m/FC 301 (A1): 50 m/ FC 302: 300m
L1, L2, L3
200-240V ±10%
4
4
50/60Hz ±5%
1)
0 - 800
Hz
0 - 300Hz
Unlimited
0.01 - 3600sec.
1)
1)
1)
1)
10 ms
1 ms
2
1.5mm
/16 AWG
2
1mm
/18 AWG
85