Electrical Installation
8.3.2 CE Compliance
Fuses or Circuit Breakers are mandatory to comply with IEC 60364. Danfoss recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V,
or 600V depending on the frequency converter voltage rating. With the proper fusing the frequency converter short circuit
current rating (SCCR) is 100,000 Arms.
Enclosure
FC 300 Power
Size
[kW]
A1
0.25-1.5
A2
0.25-2.2
A3
3.0-3.7
B3
5.5
B4
7.5-15
C3
18.5-22
C4
30-37
A4
0.25-2.2
A5
0.25-3.7
B1
5.5-7.5
B2
11
C1
15-22
C2
30-37
Table 8.2 200-240V, Frame Sizes A, B, and C
FC 300 Design Guide
Recommended
Recommended
fuse size
gG-10
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-16 (3)
gG-20 (3.7)
gG-25
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
gG-80 (18.5)
gG-150 (18.5)
aR-125 (22)
aR-160 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
gG-10 (0.25-1.5)
gG-16 (2.2)
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
gG-25 (5.5)
gG-32 (7.5)
gG-50
gG-63 (15)
gG-160 (15-18.5)
gG-80 (18.5)
aR-160 (22)
gG-100 (22)
aR-160 (30)
aR-200 (30)
aR-200 (37)
aR-250 (37)
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
Recommended circuit
Max. fuse
breaker
Moeller
gG-25
PKZM0-16
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
NZMB2-A250
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
NZMB2-A200
NZMB2-A250
Max trip level
[A]
16
25
25
50
100
150
8
250
25
25
63
100
160
250
191
8