Application Examples
If the frequency converter is at the torque limit and a stop
command is activated, terminal 29 Output (programmed to
Torque limit and stop [27]) is activated. The signal to
terminal 27 changes from 'logic 1' to 'logic 0', and the
motor starts to coast, thereby ensuring that the hoist stops
even if the frequency converter itself cannot handle the
required torque (i.e. due to excessive overload).
-
Start/stop via terminal 18
5-10 Terminal 18 Digital Input Start [8]
-
Quickstop via terminal 27
5-12 Terminal 27 Digital Input Coasting Stop,
Inverse [2]
-
Terminal 29 Output
5-02 Terminal 29 Mode Terminal 29 Mode Output
[1]
5-31 Terminal 29 Digital Output Torque Limit &
Stop [27]
-
Relay output [0] (Relay 1)
5-40 Function Relay Mechanical Brake Control [32]
9
9
12
13
External
24 VDC
234
FC 300 Design Guide
18
19
27
29
32
33
20
37
Start
I max
0.1 Amp
-
+
P 5-40 [0] [32]
Mechanical Brake
Connection
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark