General Specifications - Danfoss VLT AutomationDrive FC 300 Design Manual

90-1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 300:
Table of Contents

Advertisement

Selection

4.3 General Specifications

Mains Supply
Supply terminals (6-Pulse)
Supply terminals (12-Pulse)
Supply voltage
Supply voltage
4
4
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True power factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≥ 90 kW
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
Motor Output (U, V, W)
Output voltage
Output frequency (90-1000 kW)
Output frequency in flux mode (FC 302 only)
Switching on output
Ramp times
1)
Voltage and power dependent.
Torque Characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Torque rise time in VVC
Torque rise time in FLUX (for 5 kHz fsw)
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
Cable Lengths and Cross Sections for Control Cables
Max. motor cable length, screened
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
1)
For power cables, see 4.1 Electrical Data, 380-500 V.
Protection and Features
Electronic thermal motor protection against
overload.
70
®
VLT
AutomationDrive FC 300 Design Guide 90-1200 kW
plus
(independent of fsw)
MG34S202 - Rev. 2013-08-19
overvoltage category III/pollution degree 2
1)
L1, L2, L3
L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
380-500 V ±10%
FC 302: 525-690 V ±10%
50/60 Hz ±5%
3.0% of rated supply voltage
≥0.9 nominal at rated load
near unity (>0.98)
maximum 1 time/2 min.
0-100% of supply voltage
1)
0-590
Hz
0-300 Hz
Unlimited
0.01-3600 s
maximum 160% for 60 s
maximum 180% up to 0.5 s
maximum 160% for 60 s
maximum 110% for 60 s
10 ms
1 ms
150 m
300 m
2
1.5 mm
/16 AWG
2
1 mm
/18 AWG
0.5 mm
2
/20 AWG
2
0.25 mm
/24 AWG
1)
1)
1)
1)