Danfoss VLT AutomationDrive Design Manual page 77

Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

FC 300 Selection
Mains Supply 3 x 525- 690V AC
FC 302
High/ Normal Load*
4
4
Output current
Max. input current
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
76
FC 300 Design Guide
P37K
HO
Typical Shaft output at
30
550V [kW]
Typical Shaft output at
40
575V [HP]
Typical Shaft output at
37
690V [kW]
Enclosure IP21
D1
Enclosure IP54
D1
Enclosure IP00
D3
Continuous
48
(at 550V) [A]
Intermittent (60 sec
overload)
77
(at 550V) [A]
Continuous
46
(at 575/690V) [A]
Intermittent (60 sec
overload)
74
(at 575/690V) [A]
Continuous KVA
46
(at 550V) [KVA]
Continuous KVA
46
(at 575V) [KVA]
Continuous KVA
55
(at 690V) [KVA]
Continuous
53
(at 550V ) [A]
Continuous
51
(at 575V ) [A]
Continuous
50
(at 690V) [A]
Max. cable size, mains,
motor, load share and
2
brake [mm
(AWG)]
Max. external mains
125
fuses [A]
1
Estimated power loss
1299
at 600V [W]
4)
Estimated power loss
1002
4)
at 690V [W]
Weight,
enclosure IP21, IP54 [kg]
Weight,
enclosure IP00 [kg]
Efficiency
4)
0.97
Output frequency
Heatsink overtemp. trip
Power card ambient trip
MG.33.BD.02 - VLT
P45K
NO
HO
NO
HO
37
37
45
45
50
50
60
60
45
45
55
55
D1
D1
D3
56
56
76
76
62
90
84
122
54
54
73
73
59
86
80
117
53
53
72
72
54
54
73
73
65
65
87
87
60
60
77
77
58
58
74
74
58
58
77
77
2x70 (2x2/0)
160
1398
1459
1645
1643
1071
1071
1251
1251
0.97
0 - 600Hz
90°C
75°C
®
is a registered Danfoss trademark
P55K
P75K
NO
HO
NO
55
55
75
75
75
100
75
75
90
D1
D1
D1
D1
D3
D3
90
90
113
99
135
124
86
86
108
95
129
119
86
86
108
86
86
108
103
103
129
89
89
110
85
85
106
87
87
109
200
200
1827
1350
1599
1597
1392
1392
1648
1650
96
82
0.98
0.98
P90K
HO
NO
75
90
100
125
90
110
D1
D1
D3
113
137
170
151
108
131
162
144
108
131
108
130
129
157
110
130
106
124
109
128
250
1891
1951
0.98