FC 300 Selection
Mains Supply 6 x 380 - 500V AC, 12-Pulse
FC 302
High/ Normal Load*
Typical Shaft output at 400V [kW]
Typical Shaft output at 460V [HP]
Typical Shaft output at 500V [kW]
Enclosure IP21
Enclosure IP54
Output current
Continuous
(at 400V) [A]
Intermittent (60 sec overload)
(at 400V) [A]
Continuous
(at 460/ 500V) [A]
Intermittent (60 sec overload)
(at 460/ 500V) [A]
Continuous KVA
(at 400V) [KVA]
Continuous KVA
(at 460V) [KVA]
Continuous KVA
(at 500V) [KVA]
Max. input current
Continuous
(at 400V ) [A]
Continuous
(at 460/ 500V) [A]
Max. cable size, mains [mm
2
(AWG
2)
)]
2
Max. cable size, motor [mm
(AWG
2)
)]
2
Max. cable size, brake [mm
2)
(AWG
)
Max. external mains fuses [A]
1
Estimated power loss
at 400V [W]
4)
Estimated power loss
at 460V [W]
Weight,enclosure IP21, IP 54 [kg]
Efficiency
4)
Output frequency
Heatsink overtemp. trip
Power card ambient trip
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
FC 300 Design Guide
P250
HO
NO
HO
250
315
315
350
450
450
315
355
355
F8/F9
F8/F9
480
600
600
720
660
900
443
540
540
665
594
810
333
416
416
353
430
430
384
468
468
472
590
590
436
531
531
4x90 (3/0)
4x240
(4x500 mcm)
(4x500 mcm)
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
5164
6790
6960
4822
6082
6345
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
P315
P355
NO
HO
355
355
500
500
400
400
F8/F9
F8/F9
F8/F9
F8/F9
658
658
724
987
590
590
649
885
456
456
470
470
511
511
647
647
580
580
4x90 (3/0)
4x240 (500 mcm)
4x240
4x240
(4x500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
700
7701
7691
6953
6944
440/656
0.98
0 - 600Hz
95°C
75°C
P400
NO
HO
NO
400
400
450
600
550
600
500
500
530
F8/F9
F8/F9
745
695
800
820
1043
880
678
678
730
746
1017
803
516
482
554
540
540
582
587
587
632
733
684
787
667
667
718
4x240 (500 mcm)
4x240
(4x500 mcm)
2 x 185
(2 x 350 mcm)
8879
8178
9670
8089
8085
8803
69
4
4