Electrical Installation
Make the screen connections with the largest possible
surface area (cable clamp). This is done by using the
supplied installation devices within the frequency
converter.
Cable-length and cross-section:
The frequency converter has been EMC tested with a given
length of cable. Keep the motor cable as short as possible
to reduce the noise level and leakage currents.
Switching frequency:
When frequency converters are used together with Sine-
wave filters to reduce the acoustic noise from a motor, the
switching frequency must be set according to the
instruction in 14-01 Switching Frequency.
Term.
96
97
no.
U
V
U1
V1
W2 U2
U1
V1
8
8
1)
Protected Earth Connection
CAUTION
In motors without phase insulation paper or other
insulation reinforcement suitable for operation with
voltage supply (such as a frequency converter), fit a Sine-
wave filter on the output of the frequency converter.
170
FC 300 Design Guide
98
99
W
1)
Motor voltage 0-100% of mains voltage.
PE
3 wires out of motor
W1
Delta-connected
1)
PE
V2
6 wires out of motor
W1 PE
1)
Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected
separately.