Danfoss VLT AutomationDrive Design Manual page 233

Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
9
9
05
06
Table 9.13 Using SLC to Set a Relay
232
FC 300 Design Guide
Parameters
Function
Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
100RPM
Feedback Speed
Error
4-32 Motor
5 sec
Feedback Loss
Timeout
7-00 Speed PID
[2] MCB 102
Feedback Source
17-11 Resolution
1024*
(PPR)
13-00 SL
[1] On
Controller Mode
13-01 Start Event [19] Warning
13-02 Stop Event [44] Reset
key
13-10 Comparato
[21] Warning
r Operand
no.
13-11 Comparato
[1] ≈*
r Operator
13-12 Comparato
90
r Value
13-51 SL
[22]
Controller Event
Comparator 0
13-52 SL
[32] Set
Controller Action
digital out A
low
5-40 Function
[80] SL digital
Relay
output A
* = Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in the
case that Warning 90 becomes
TRUE then Relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 sec. then the drive
continues and the warning
disappears. But Relay 1 will still
be triggered until [Reset] on
the LCP.
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
Table 9.14 Mechanical Brake Control
1-76
Current
Speed
1-71
Start (18)
Start
reversing (19)
Relay output
Open
Closed
Parameters
Function
Setting
5-40 Function
[32] Mech.
Relay
brake ctrl.
5-10 Terminal 18
[8] Start*
Digital Input
5-11 Terminal 19
[11] Start
Digital Input
reversing
1-71 Start Delay
0.2
1-72 Start
[5] VVC+/
Function
FLUX
Clockwise
1-76 Start
Im,n
Current
2-20 Release
App.
Brake Current
dependent
2-21 Activate
Half of
Brake Speed
nominal slip
[RPM]
of the motor
* = Default Value
Notes/comments:
Time
2-21
1-71
2-21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt fc 300

Table of Contents