Danfoss VLT FC 300 Operating Instructions Manual
Danfoss VLT FC 300 Operating Instructions Manual

Danfoss VLT FC 300 Operating Instructions Manual

Automation drive
Hide thumbs Also See for VLT FC 300:

Advertisement

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 300 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss VLT FC 300

  • Page 1: Table Of Contents

    3.4.1 Start/Stop 3.4.2 Pulse Start/Stop 3.5.1 Electrical Installation, Control Cables 3.5.2 Switches S201, S202, and S801 3.6 Final Set-Up and Test 3.7 Additional Connections 3.7.1 Mechanical Brake Control 3.7.3 Motor Thermal Protection ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 2 4 How to Programme 4.1.1 How to Programme on the Graphical LCP 4.2 Quick Setup 4.3 Parameter Lists 5 General Specifications 6 Warnings and Alarms 6.1 Warning and Alarm Definitions Index ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 3: How To Read These Operating Instructions

    X = Revision number YY = Language code These Operating Instructions will help you get started, install, program, and troubleshoot your frequency Danfoss technical literature is also available online at converter. www.danfoss.com/drives. Symbols Chapter 1, How to Read these Operating Instructions, The following symbols are used in this manual.
  • Page 4: Abbreviations

    Rated Inverter Output Current Revolutions Per Minute Regenerative terminals Regen Second sec. Synchronous Motor Speed Torque limit Volts The maximum output current VLT,MAX The rated output current supplied by the VLT,N frequency converter ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 5: Safety Instructions And General Warning

    RCD Application Note MN90GX02 (x=version number). Installation in high altitudes Protective earthing of the frequency converter and the use 380-500 V: At altitudes above 3 km, please contact Danfoss of RCDs must always follow national and local regulations. regarding PELV.
  • Page 6: Avoid Unintended Start

    Illustration 2.2 shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1). The circuit interrupt is caused by an opening door contact. The illustration also shows how to connect a non-safety related hardware coast. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 7: It Mains

    If this is done it will reduce the RFI performance to A2 level. For the 525 - 690V frequency converters, 14-50 RFI Filter has no function. The RFI switch cannot be opened. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 8: How To Install

    Remove the box and handle the frequency converter on the pallet, as long as possible. Illustration 3.2 Recommended lifting method, frame size F9/F10. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 9 The angle from the top of the frequency converter to the lifting cable should be 60° or greater. In addition to the drawings above a spreader bar is an acceptable way to lift the F Frame. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 10: Mechanical Dimensions

    ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power 3.1.5 Mechanical Dimensions 1497 2205 2280 1497 2205 2280 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 11 ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power 1497 2205 2280 1497 2205 2280 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 12 ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power 1497 2205 2280 1497 2205 2280 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 13 ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 14 The F9 is an F8 with an additional options cabinet. The F11 is an F10 with an additional options cabinet. The F13 is an F12 with an additional options cabinet. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 15: Mechanical Installation

    NOTE All cable lugs/shoes must mount within the width of the terminal bus bar. (22.8) (30.6) Illustration 3.5 Space in front of IP21/IP54 enclosure type, frame size F9 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 16: Terminal Locations, F8-F14 - 12-Pulse

    Illustration 3.11 Terminal locations - Inverter and Rectifier Cabinet - F8 and F9 (front, left and right side view). The gland plate is 42 mm below .0 level. 1) Earth ground bar ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 17 Illustration 3.12 Terminal locations - Inverter Cabinet (front, left and right side view). The gland plate is 42 mm below .0 level. 1) Earth ground bar 2) Motor terminals 3) Brake terminals ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 18 W/T3 98 180.3 [7.10] 0.0 [0.00] Illustration 3.13 Terminal locations - Inverter Cabinet (front, left and right side view). The gland plate is 42 mm below .0 level. 1) Earth ground bar ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 19 253.1 [10.0] EARTH GROUND 180.3 [7.1] .0 [.0] MOTOR BRAKE Illustration 3.14 Terminal Locations - Inverter Cabinet (left, front, and side view). The gland plate is 42 mm below .0 level. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 20 Illustration 3.15 Terminal locations - Rectifier (Left side, front and right side view). The gland plate is 42 mm below .0 level. 1) Loadshare Terminal (-) 2) Earth ground bar 3) Loadshare Terminal (+) ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 21 .0 [.0] .0 [.0] MAINS MOTOR SIDE MAINS SIDE Illustration 3.16 Terminal Locations - Rectifier (Left side, front and right side view). The gland plate is 42 mm below .0 level. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 22 Illustration 3.17 Terminal locations - Options Cabinet (Left side, front and right side view). Terminal locations - Options Cabinet Frame Size F11/F13 547.8 440.4 151.3 244.4 Illustration 3.18 Terminal locations - Options Cabinet (Left side, front and right side view). ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 23: Cooling And Airflow

    If additional duct work is added externally to the Rittal cabinet the pressure drop in the ducting must be calculated. Use the charts below to derate the frequency converter according to the pressure drop. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 24 [ 1 . 437 ] 733 . 0 [ 1 . 466 ] [ 28 . 858 ] 800 . 0 [ 31. 496 ] 1533 . 0 [ 60 . 354 ] ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 25 37.2 [.69] [1.47] 733.0 36.5 [28.86] [1.44] 800.0 [31.50] 1533.0 [60.35] 2333.0 [91.85] F8-F14: Cable entries viewed from the bottom of the frequency converter - 1) Place conduits in marked areas ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 26: Field Installation Of Options

    Associated with each set-point is an SPDT circuit breaker or disconnect switch. alarm relay for external use. Requires an external “window- type” current transformer (supplied and installed by customer). ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 27: Electrical Installation

    3.3 Electrical Installation Guide, MG33BXYY. 3.3.1 Transformer Selection See 5.1 General Specifications for correct dimensioning of motor cable cross-section and length. The frequency converter must be used with a 12-pulse isolation transformer. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 28 6-pulse rectifier. Contact factory for reconnection details. 4) No paralleling of mains cabling is shown here. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 29 In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply (such as a frequency converter), fit a Sine- wave filter on the output of the frequency converter. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 30 Mains / Fuses L1-1 L2-1 L3-1 Brake Terminals 91-1 92-1 93-1 Mains / Fuses Inverter Module L2-1 L2-2 L3-2 SCR Enable / Disable 91-2 92-2 93-2 Relay 1 Relay 2 Auxillary Fan ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 31 AUX Fan L1-1 L2-1 L3-1 L1-2 L2-2 L3-2 DC Bus Connections for common DC Bus Mains Fuses F10/F12 (6 Pieces) DC+ DC- DC Bus Connections for common DC Bus DC+ DC- ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 32 Illustration 3.25 Rectifier Cabinet, frame size F14 12-Pulse Rectifier Modules Mains L1-1 L2-1 L3-1 L1-2 L2-2 L3-2 DC Busbar Access DC Busbar Access 100 101 102 103 L2 L1 Mains Fuses (6 pieces) ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 33 NAMUR NAMUR Fuse. See fuse tables for part numbers AUX Fan Fan Fuses. See fuse tables for part numbers 101 102 103 SMPS Fuses. See fuse tables for part numbers Brake ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 34 NAMUR NAMUR Fuse. See 3.3.13 Fuses for part numbers AUX Fan Fan Fuses. See 3.3.13 Fuses for part numbers 101 102 103 SMPS Fuses. See 3.3.13 Fuses for part numbers Brake ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 35 ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power Illustration 3.28 Inverter Cabinet, frame size F14 AUX Fan Motor 101 102 Brake ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 36 See fuse tables for part numbers 3) Mains/6 phase Mains Fuses, (6 pieces) See fuse tables for part numbers 91-1 92-1 93-1 91-2 92-2 93-2 2 x 3-phase manual disconnect L1-1 L2-1 L3-1 L1-2 L2-2 L3-2 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 37 See fuse tables for part numbers 3) Mains/6 phase Mains Fuses, (6 pieces) See fuse tables for part numbers 91-1 92-1 93-1 91-2 92-2 93-2 2 x 3-phase manual disconnect L1-1 L2-1 L3-1 L1-2 L2-2 L3-2 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 38 Table 3.2 Tightening torques on the frequency converter and 14-50 RFI Filter on the filter. For further reference, see IEC 364-3. In case optimum EMC performance is needed, parallel motors are connected ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 39: Shielded Cables

    Operating Instructions High Power 3.3.7 Shielded Cables WARNING Danfoss recommends to use shielded cables between the LCL filter and the AFE unit. Unshielded cables can be between transformer and LCL filter input side. It is important that shielded and armoured cables are connected in a proper way to ensure the high EMC immunity and low emissions.
  • Page 40: Mains Connection

    If the unit is without built-in fuses, ensure that the appropriate fuses have the correct current rating. F Frame Requirements The brake resistor(s) must be connected to the brake terminals in each inverter module. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 41 100 and 101. A 5A fuse should be used for protection. In UL applications this should be LittleFuse KLK-5 or equivalent. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 42: Fuses

    The frequency converter must be protected against short- The fuses below are suitable for use on a circuit capable of circuit to avoid electrical or fire hazard. Danfoss delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or recommends using the fuses mentioned below to protect...
  • Page 43 15 A, 600 V Table 3.10 30 A Fuse Protected Terminal Fuse 380-500 V P500-P1M2, KLK-15 15 A, 600 V 525-690 V P500-P1M4, KLK-15 15 A, 600 V 525-690 V Table 3.9 Fan Fuses ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 44 Table 3.12 NAMUR Fuse Alternative Frame size Bussmann PN* Rating Fuses F8-F14 LP-CC-6 6 A, 600 V Any listed Class CC, 6 A Table 3.13 Safety Relay Coil Fuse with Pilz Relay ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 45: Motor Bearing Currents

    Make a direct earth connection between grounding of the frequency converter, motor, driven the motor and load motor machine, and motor to the driven machine is required. Lower the IGBT switching frequency ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 46: Control Cable Routing

    The cable must be placed in the provided path inside the frequency converter and tied down together To remove the cable from the terminal: with other control wires. Insert a screw driver in the square hole. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 47 ® Automation Drive FC 300 12-Pulse How to Install Operating Instructions High Power Pull out the cable. Max. 0.4 x 2.5 mm ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 48: Connection Examples

    Terminal 53, High Ref./Feedback = 1500 RPM Switch S201 = OFF (U) Start Stop inverse Safe Stop Speed Speed RPM 39 42 53 54 P 6-15 Ref. voltage P 6-11 10V Start (18) Start (27) ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 49: Electrical Installation, Control Cables

    11 12 13 14 11 12 13 14 11 12 13 14 15 16 17 18 15 16 17 18 15 16 17 18 15 16 17 18 15 16 17 18 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 50 Design Guide. See also sections Safe Stop and Safe Stop Installation. 1) F8/F9 = (1) set of terminals. 2) F10/F11 = (2) sets of terminals. 3) F12/F13 = (3) sets of terminals. 4) F14 = (4) sets of terminals. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 51 FC 300 Operating Instructions, MG33AXYY. PNP (Source) Remember to connect the shields in a proper way to ensure optimum electrical immunity. Digital input wiring NPN (Sink) Digital input wiring NOTE Control cables must be screened/armoured. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 52: Switches S201, S202, And S801

    Choose between complete or reduced AMA. If a Sine-wave filter is mounted, run only the reduced AMA, or remove the Sine-wave filter during the AMA procedure. Press [OK]. The display shows “Press [Hand on] to start”. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 53: Additional Connections

    This number along with the description of the alarm will assist you in troubleshooting. If contacting Danfoss for service, make sure to mention number and alarm description. NOTE Unsuccessful AMA is often caused by incorrectly registered...
  • Page 54: Motor Thermal Protection

    Provide further motor protection by e.g. thermistors in each motor or individual thermal relays (circuit breakers are not suitable as protection). LC lter Illustration 3.34 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 55: How To Programme

    Line 1-2: Operator data lines displaying data defined or chosen by the user. By pressing the [Status] key, up to one extra line can be added. Status line: Status messages displaying text. Warn. Alarm Hand Auto Reset ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 56 Set the ramping down time 3-42 Ramp 1 Ramp Down Time with reference to synchronous motor speed, n Set the site from where the 3-13 Reference Site reference must work ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 57: Quick Setup

    Part of Language package 3 running. Thai Part of Language package 2 Bahasa Indonesia Part of Language package 2 [52] Hrvatski 1-20 Motor Power [kW] Range: Function: Application dependent [Application dependant] ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 58 "Press [OK] to • The choice of configu- finish AMA". After pressing [OK], the frequency ration in 1-00 Configuration converter is ready for operation. Mode: for [1] Speed closed ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 59 0.01 s in speed mode. See ramp-up time in 3-41 Ramp 1 Ramp up Time. t dec s x n s RPM Par . 3 − 42 = ref RPM ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 60 34-** MCO Data Readout parameters 4-** Limits Warnings, setting of limits and warning 35-** Sensor Input Option parameters 5-** Digital inputs and outputs, includes relay controls 6-** Analog inputs and outputs ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 61 Quick Menu Password 200 N/A 1 set-up TRUE Int16 0-66 Access to Quick Menu w/o Password [0] Full access 1 set-up TRUE Uint8 0-67 Bus Password Access 0 N/A All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 62 U/f Characteristic - F App.Dependent All set-ups TRUE Uint16 1-58 Flystart Test Pulses Current 30 % All set-ups FALSE Uint16 1-59 Flystart Test Pulses Frequency 200 % All set-ups FALSE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 63 KTY Threshold level 80 °C 1 set-up TRUE Int16 1-98 ATEX ETR interpol. points freq. App.Dependent 1 set-up TRUE Int16 1-99 ATEX ETR interpol points current App.Dependent 2 set-ups TRUE Int16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 64 TRUE Uint16 2-26 Torque Ref 0.00 % All set-ups TRUE Int16 2-27 Torque Ramp Time 0.2 s All set-ups TRUE Uint8 2-28 Gain Boost Factor 1.00 N/A All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 65 All set-ups TRUE Uint8 3-77 Ramp 4 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE Uint8 3-78 Ramp 4 S-ramp Ratio at Decel. End 50 % All set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 66 [0] Off All set-ups TRUE Uint8 3-93 Maximum Limit 100 % All set-ups TRUE Int16 3-94 Minimum Limit -100 % All set-ups TRUE Int16 3-95 Ramp Delay App.Dependent All set-ups TRUE TimD ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 67 Uint16 4-61 Bypass Speed From [Hz] App.Dependent All set-ups TRUE Uint16 4-62 Bypass Speed To [RPM] App.Dependent All set-ups TRUE Uint16 4-63 Bypass Speed To [Hz] App.Dependent All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 68 Term. 33 Low Ref./Feedb. Value backUnit All set-ups TRUE Int32 5-58 Term. 33 High Ref./Feedb. Value App.Dependent All set-ups TRUE Int32 5-59 Pulse Filter Time Constant #33 100 ms All set-ups FALSE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 69 Pulse Out #29 Timeout Preset 0.00 % 1 set-up TRUE Uint16 5-97 Pulse Out #X30/6 Bus Control 0.00 % All set-ups TRUE 5-98 Pulse Out #X30/6 Timeout Preset 0.00 % 1 set-up TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 70 Terminal X30/8 Max. Scale 100.00 % All set-ups TRUE Int16 6-63 Terminal X30/8 Bus Control 0.00 % All set-ups TRUE 6-64 Terminal X30/8 Output Timeout Preset 0.00 % 1 set-up TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 71 Terminal X45/3 Max. Scale 100.00 % All set-ups TRUE Int16 6-83 Terminal X45/3 Bus Control 0.00 % All set-ups TRUE 6-84 Terminal X45/3 Output Timeout Preset 0.00 % 1 set-up TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 72 Process PID Feed Fwd Ramp down 0.01 s All set-ups TRUE Uint32 7-56 Process PID Ref. Filter Time 0.001 s All set-ups TRUE Uint16 7-57 Process PID Fb. Filter Time 0.001 s All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 73 Slave Error Count 0 N/A All set-ups TRUE Uint32 8-9* Bus Jog 8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE Uint16 8-91 Bus Jog 2 Speed App.Dependent All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 74 Uint16 9-93 Changed parameters (4) 0 N/A All set-ups FALSE Uint16 9-94 Changed parameters (5) 0 N/A All set-ups FALSE Uint16 9-99 Profibus Revision Counter 0 N/A All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 75 10-39 Devicenet F Parameters 0 N/A All set-ups TRUE Uint32 10-5* CANopen 10-50 Process Data Config Write. App.Dependent 2 set-ups TRUE Uint16 10-51 Process Data Config Read. App.Dependent 2 set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 76 12-5* EtherCAT 12-50 Configured Station Alias 0 N/A 1 set-up FALSE Uint16 12-51 Configured Station Address 0 N/A All set-ups TRUE Uint16 12-59 EtherCAT Status 0 N/A All set-ups TRUE Uint32 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 77 [0] Broadcast only 2 set-ups TRUE Uint8 12-96 Port Mirroring null 2 set-ups TRUE Uint8 12-98 Interface Counters 4000 N/A All set-ups TRUE Uint32 12-99 Media Counters 0 N/A All set-ups TRUE Uint32 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 78 Uint8 13-44 Logic Rule Boolean 3 null 2 set-ups TRUE Uint8 13-5* States 13-51 SL Controller Event null 2 set-ups TRUE Uint8 13-52 SL Controller Action null 2 set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 79 FALSE Uint8 14-56 Capacitance Output Filter App.Dependent All set-ups FALSE Uint16 14-57 Inductance Output Filter App.Dependent All set-ups FALSE Uint16 14-59 Actual Number of Inverter Units App.Dependent 1 set-up FALSE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 80 14-80 Option Supplied by External 24VDC [1] Yes 2 set-ups FALSE Uint8 14-89 Option Detection [0] Protect Option Config. 1 set-up TRUE Uint8 14-9* Fault Settings 14-90 Fault Level null 1 set-up TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 81 VisStr[20] Frequency Converter Serial 15-51 Number 0 N/A All set-ups FALSE VisStr[10] 15-53 Power Card Serial Number 0 N/A All set-ups FALSE VisStr[19] 15-59 CSIV Filename App.Dependent 1 set-up FALSE VisStr[16] ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 82 All set-ups FALSE Uint16 15-93 Modified Parameters 0 N/A All set-ups FALSE Uint16 15-98 Drive Identification 0 N/A All set-ups FALSE VisStr[40] 15-99 Parameter Metadata 0 N/A All set-ups FALSE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 83 FALSE Int16 0.000 ReferenceFeed- 16-52 Feedback [Unit] backUnit All set-ups FALSE Int32 16-53 Digi Pot Reference 0.00 N/A All set-ups FALSE Int16 16-57 Feedback [RPM] 0 RPM All set-ups FALSE Int32 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 84 FALSE Uint32 16-92 Warning Word 0 N/A All set-ups FALSE Uint32 16-93 Warning Word 2 0 N/A All set-ups FALSE Uint32 16-94 Ext. Status Word 0 N/A All set-ups FALSE Uint32 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 85 17-59 Resolver Interface [0] Disabled All set-ups FALSE Uint8 17-6* Monitoring and App. 17-60 Feedback Direction [0] Clockwise All set-ups FALSE Uint8 17-61 Feedback Signal Monitoring [1] Warning All set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 86 18-91 Process PID Output 0.0 % All set-ups FALSE Int16 18-92 Process PID Clamped Output 0.0 % All set-ups FALSE Int16 18-93 Process PID Gain Scaled Output 0.0 % All set-ups FALSE Int16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 87 Int32 30-81 Brake Resistor (ohm) App.Dependent 1 set-up TRUE Uint32 30-83 Speed PID Proportional Gain App.Dependent All set-ups TRUE Uint32 30-84 Process PID Proportional Gain 0.100 N/A All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 88 32-50 Source Slave [2] Encoder 2 2 set-ups TRUE Uint8 32-51 MCO 302 Last Will [1] Trip 2 set-ups TRUE Uint8 32-52 Source Master [1] Encoder 1 X56 2 set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 89 32-88 Dec. up for limited jerk 0 ms 2 set-ups TRUE Uint32 32-89 Dec. down for limited jerk 0 ms 2 set-ups TRUE Uint32 32-9* Development 32-90 Debug Source [0] Controlcard 2 set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 90 33-45 Time in Target Window 0 ms 2 set-ups TRUE Uint8 33-46 Target Window LimitValue 1 N/A 2 set-ups TRUE Uint16 33-47 Size of Target Window 0 N/A 2 set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 91 [20] 125 Kbps 2 set-ups TRUE Uint8 33-94 X60 MCO RS485 serial termination [0] Off 2 set-ups TRUE Uint8 33-95 X60 MCO RS485 serial baud rate [2] 9600 Baud 2 set-ups TRUE Uint8 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 92 0 N/A All set-ups TRUE Uint16 34-7* Diagnosis readouts 34-70 MCO Alarm Word 1 0 N/A All set-ups FALSE Uint32 34-71 MCO Alarm Word 2 0 N/A All set-ups FALSE Uint32 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 93 35-44 Term. X48/2 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE Int32 35-45 Term. X48/2 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE Int32 35-46 Term. X48/2 Filter Time Constant 0.001 s All set-ups TRUE Uint16 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 94: General Specifications

    Voltage level, logic '1' NPN < 14 V DC Maximum voltage on input 28 V DC Pulse frequency range 0 - 110 kHz (Duty cycle) Min. pulse width 4.5 ms Input resistance, R approx.4 kΩ ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 95 Max. error 0.5% of full scale Bandwidth 100 Hz The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. PELV isolation +24V Control Mains High Motor voltage Functional isolation DC-Bus RS485 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 96 Control card, 10 V DC output Terminal number Output voltage 10.5 V±0.5 V Max. load 15 mA The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 97 0-6000 rpm: error ±0.15 rpm Speed accuracy (closed loop), depending on resolution of feedback device Torque control accuracy (speed feedback) max error±5% of rated torque All control characteristics are based on a 4-pole asynchronous motor ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 98 As a response to a critical level, the frequency converter can adjust the switching frequency and/ or change the switching pattern in order to ensure the performance of the frequency converter. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 99 0 - 600 Hz Heatsink overtemp. trip 95° C Power card ambient trip 75° C * High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 100 Output frequency 0-600 Hz Heatsink overtemp. trip 95° C Power card ambient trip 75° C * High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 101 0 - 500 Hz Heatsink overtemp. trip 85° C Power card ambient trip 75° C * High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 102 Output frequency 0-500 Hz Heatsink overtemp. trip 85° C Power card ambient trip 75° C * High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 103 30 W to the losses. (Though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each). Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (±5%). ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 104: Warnings And Alarms

    The intermediate circuit voltage (DC) is higher than the rating, the counter should decrease. high voltage warning limit. The limit is dependent on the frequency converter voltage rating. The unit is still active. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 105 If using a KTY sensor, check the programming of your Danfoss supplier: 1-95 KTY Sensor Type, 1-96 KTY Thermistor Resource, and 1-97 KTY Threshold level match 15-40 FC Type sensor wiring. 15-41 Power Section 15-42 Voltage ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 106 Rectifier warning appears. The frequency converter is still module. operational but without the brake function. Remove power ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 107 Check for loose or missing wiring 2096-2104 H983x: option in slot x has issued a legal powerup-wait It may be necessary to contact your Danfoss supplier or 2304 Could not read any data from power EEPROM service department. Note the code number for further...
  • Page 108 5124 Option in slot B: Hardware incompatible with ALARM 50, AMA calibration failed Control board hardware. Contact your Danfoss supplier or Danfoss Service 5125 Option in slot C0: Hardware incompatible with Department. control board hardware. ALARM 51, AMA check U...
  • Page 109 24 V DC to terminal 37, then send a reset signal (via manual reset. Reset the unit to clear the alarm. Bus, Digital I/O, or by pressing the reset key). ALARM 81, CSIV corrupt CSIV file has syntax errors. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 110 2 = right inverter module in F10 or F11 frame sizes. 5 = rectifier module. 2 = second drive from the left inverter module in 6 = right rectifier module in F14 frame size. F14 frame size. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 111 Reset the frequency converter for normal operation. WARNING 251, New typecode The power card or other components have been replaced and the typecode changed. Reset to remove the warning and resume normal operation. ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 112 Input....................105 Inputs:....................94 Output....................96 Main Reactance..................58 Disposal Instruction................3 Mains Drives With Factory Installed Brake Chopper Option..... 40 Connection..................40 Supply (L1, L2, L3)................94 Duct Cooling..................23 ® MG34Q202 - VLT is a registered Danfoss trademark...
  • Page 113 Repair Work....................5 Reference Via A Potentiometer........... 48 Reset....................104, 109 Residual Current Device............... 5 RFI Switch....................38 Warning And Alarm Definitions............ 104 Wire Access..................... 15 Safe Stop......................6 Stop Installation.................. 6 ® MG34Q202 - VLT is a registered Danfoss trademark...

Table of Contents