How to Order
FC 302 - Mains: 525-690V (T7) - 40% Duty Cycle
FC 302
T7
P37K
P45K
P55K
P75K
P90K
5
5
P110
P132
P160
P200
P250
P315
Abbreviations for the Tables
*) Resulting max. brake torque when using R
in brackets is the drives max. brake torque
2
*) All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
(60/75°C) conductors are recommended.
3
*) Order the specified amount of Brake Resistors (e.g. 2 x 1062 = 2 pieces of 175U1062). See table header for the first four
characters (175U or 130B).
4
*) Rating for each thermistor relay (using one thermistor relay per resistor).
5
*) Parallel star connection (see the Installation chapter).
6
*) Please contact Danfoss for further info.
7
*) With Klixon Switch
P
m
R
min
R
rec
P
b, max
Therm. relay
Code number
Cable cross section
P
pbr,avg
R
br,avg
110
FC 300 Design Guide
P
R
R
R
m
min
br. nom
rec
(HO)
[kW]
[Ω]
[Ω]
[Ω]
37
18
23.5
22
45
13.5
19.3
18
55
13.5
15.8
15
75
8.8
11.5
11
90
8.8
9.6
9.1
110
6.6
7.8
7.5
132
4.2
6.5
6.2
160
4.2
5.4
5.1
200
3.4
4.3
7.8 / 2 = 3.9
250
2.3
3.4
6.6 / 2 = 3.3
315
2.3
2.7
5.4 / 2 = 2.7
rec
: Rated motor size for VLT type
: Minimum permissible brake resistor - by drive
: Recommended brake resistor (Danfoss)
: Brake resistor rated power as stated by supplier
: Brake current setting of thermal relay
: Order numbers for Danfoss Brake Resistors
: Recommended minimum value based upon PVC insulated copper cable, 30 degree Celsius ambient temperature
with normal heat dissipation
: Brake Resistor average rated power as stages by
: The nominal (recommended) resistor value to ensure a brake power on motor shaft of 160%/110% for 1 minute
MG.33.BD.02 - VLT
P
Order no.
br avg
[kW]
130Bxxxx
28
2118
33
2119
42
2120
56
2121
66
2122
78
2123
96
2124
120
2125
2 x 78
2 x 2126
2 x 90
2 x 2127
2 x 112
2 x 2128
. Using the R
will result in maximum brake torque e.g. 160%. The value
br,nom
®
is a registered Danfoss trademark
Period Cable cross
Therm.
section
Relay
[s]
[mm2]
[A]
600
6
35
600
10
42
600
16
52
600
25
71
600
35
85
600
50
102
600
50
124
600
70
198
600
2 x 25
200
3
*
3
600
2 x 35
234
*
3
600
2 x 50
288
*
Max. brake
torque with
R
*
rec
[%]
150 (150)
150 (150)
150 (150)
150 (150)
146 (150)
150 (150)
150 (150)
150 (150)
150 (150)
150 (150)
150 (150)