Danfoss VLT AutomationDrive Design Manual page 232

Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

Application Examples
S p e e d
R e f e r e n c e
S t a r t ( 1 8 )
F r e e z e r e f ( 2 7 )
S p e e d u p ( 2 9 )
S p e e d d o w n ( 3 2 )
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
RS-485
06
61
+
68
69
-
Table 9.11 RS-485 Network Connection
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
FC 300 Design Guide
Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
FC
+24 V
12
1-90 Motor
+24 V
13
D IN
18
Thermal
D IN
19
Protection
COM
20
1-93 Thermistor
D IN
27
Source
D IN
29
* = Default Value
D IN
32
D IN
33
Notes/comments:
D IN
37
If only a warning is desired,
1-90 Motor Thermal Protection
+10 V
50
should be set to [1] Thermistor
A IN
53
warning.
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 9.12 Motor Thermistor
Parameters
Function
Setting
[2]
Thermistor
trip
[1] Analog
input 53
231
9
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt fc 300

Table of Contents