FC 300 Selection
Mains Supply 3 x 380 - 500VAC
FC 302
High/ Normal Load*
Typical Shaft output at 400V
[kW]
Typical Shaft output at 460V
[HP]
Typical Shaft output at 500V
[kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 400V) [A]
Intermittent (60 sec
overload)
(at 400V) [A]
Continuous
(at 460/ 500V) [A]
Intermittent (60 sec
overload)
(at 460/ 500V) [A]
Continuous kVA
(at 400V) [kVA]
Continuous kVA
(at 460V) [kVA]
Continuous kVA
(at 500V) [kVA]
Max. input current
Continuous
(at 400V ) [A]
Continuous
(at 460/ 500V) [A]
Max. cable size, mains,
motor and load share [mm
(AWG
2)
)]
Max. cable size, brake [mm
(AWG
2)
)
Max. external mains fuses
1
[A]
Estimated power loss
at 400V [W]
Estimated power loss
at 460V [W]
Weight,
enclosure IP21, IP 54 [kg]
Weight,
enclosure IP00 [kg]
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
* High overload = 160% torque during 60 sec., Normal overload = 110% torque during 60 sec.
FC 300 Design Guide
P250
HO
250
350
315
E1
E1
E2
480
720
443
665
333
353
384
472
436
4x240
2
(4x500 mcm)
2
2 x 185
(2 x 350 mcm)
700
5059
4)
4822
263
221
4)
®
MG.33.BD.02 - VLT
is a registered Danfoss trademark
P315
NO
HO
NO
315
315
355
450
450
500
355
355
400
E1
E1
E2
600
600
658
660
900
724
540
540
590
594
810
649
416
416
456
430
430
470
468
468
511
590
590
647
531
531
580
4x240
(4x500 mcm)
2 x 185
(2 x 350 mcm)
900
6705
6794
7532
6082
6345
6953
270
234
0.98
0 - 600 Hz
110 °C
75 °C
P355
P400
HO
NO
HO
NO
355
400
400
450
500
600
550
600
400
500
500
530
E1
E1
E1
E1
E2
E2
658
745
695
800
987
820
1043
880
590
678
678
730
885
746
1017
803
456
516
482
554
470
540
540
582
511
587
587
632
647
733
684
787
580
667
667
718
4x240
4x240
(4x500 mcm)
(4x500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
900
900
7498
8677
7976
9473
6944
8089
8085
7814
272
313
236
277
4
4
67