Bit 14 = '0': The motor current is lower than the torque
limit selected in 4-18 Current Limit. Bit 14 = '1': The torque
limit in 4-18 Current Limit is exceeded.
Bit 15, Timer OK/limit exceeded:
Bit 15 = '0': The timers for motor thermal protection and
thermal protection are not exceeded 100%. Bit 15 = '1':
One of the timers exceeds 100%.
11.12.3 Bus Speed Reference Value
Speed reference value is transmitted to the frequency converter in a relative value in %. The value is transmitted in the form
of a 16-bit word; in integers (0-32767) the value 16384 (4000 Hex) corresponds to 100%. Negative figures are formatted by
means of 2's complement. The Actual Output frequency (MAV) is scaled in the same way as the bus reference.
Master-slave
CTW
Slave-master
STW
The reference and MAV are scaled as follows:
Par.3-00 set to
11
11
(1) -max- +max
Par.3-00 set to
(0) min-max
270
FC 300 Design Guide
16bit
Speed ref.
Actual output
freq.
-100%
(C000hex)
Reverse
Par.3-03
Max reference
®
MG.33.BD.02 - VLT
All bits in the STW are set to '0' if the connection between
the Interbus option and the frequency converter is lost, or
an internal communication problem has occurred.
0%
(0hex)
Forward
0
0%
(0hex)
Forward
Par.3-02
Min reference
is a registered Danfoss trademark
100%
(4000hex)
Par.3-03
Max reference
100%
(4000hex)
Par.3-03
Max reference