B
Parameterisation examples
B.3

Stand-alone mode

Application
The MSE6-E2M can also be used as individual device without using the device-specific network (no
network communication). The setting of all parameters must be made in this case exclusively via the
diagnostic interface of the integrated bus node. After the corresponding parameters have been set
once, the auto blocking function is automatically activated every time the power supply is switched on
(Power ON). After the MSE6-E2M has automatically switched to the blocking state, the power supply
has to be switched off and on (Power OFF/ON) for resetting the pressurisation state.
Procedure
For stand-alone mode, the following settings must be made via the diagnostic interface of the integ­
rated bus node:
1. Set system parameters.
– System parameter "Force mode": Enabled
– System parameter "System start": Saved parameters
2. Set E2M module parameters.
– Module parameter: "Auto shut-off delay"
– Module parameter "Auto shut-off low flow limit"
3. Set force value of output word Am.1.0 "Modul control".
– Bit B1=1 Activation of the automatic blocking function (Auto shut-off ) or Am.1.0 = 0x0002
A detailed description of the system parameters can be found in the CPX system descrip­
tion (è Tab. 1).
Information on the Force function can be found in the following section
(è A General fundamentals on system parameterisation).
114
Festo – MSE6-E2M-SY-EN – 1703d – English