4
Commissioning
Setting the station number and diagnostic mode (DIL switch 3)
Station numbers may only be assigned once per controller.
Recommendation:
• Assign station numbers in ascending order. Assign the station numbers in accordance
with the machine structure of the system.
Setting DIL switch 3
DIL 3.8
DIL 3.7
DIL 3.6
DIL 3.5
DIL 3.4
DIL 3.3
DIL 3.2
DIL 3.1
1) If device-related diagnostics are deactivated, then no device-related diagnostic information about the MSE6-E2M will be sent to
the master system.
Tab. 4.6 Setting the station number and diagnostic mode (DIL switch 3)
Example for setting station number 23 and activating device-related diagnostics
DIL 3.8: ON
DIL 3.7: OFF
DIL 3.6: OFF
DIL 3.5: ON
DIL 3.4: OFF
DIL 3.3: ON
DIL 3.2: ON
DIL 3.1: ON
Tab. 4.7 Setting the station number and diagnostic mode (example)
26
Setting the station number and diagnostic mode
Device-specific diagnostics
ON = activated (factory setting)
OFF = deactivated
Station number
The station number of the MSE6-E2M is set binary coded using
DIL switches 3.1 ... 3.7.
Permissible station numbers: 1 ... 125
Factory setting: 3
Example: è Tab. 4.7
Device-related diagnosis activated.
6
2
= 64
Example:
0
1
5
2
+ 2
+ 2
2
= 32
4
2
= 16
è Station number set = 23
3
2
= 8
2
2
= 4
1
2
= 2
0
2
= 1
2
4
+ 2
= 1 + 2 + 4 + 16 = 23