Parameterisation
7.2

Parameterisation information

Detailed parameterisation information can be found in the CPX system description
(è Tab. 1).
General notes on parameterisation
The characteristics of the MSE6-E2M can be parameterised.
Due to calculations that are necessary in some cases, modified parameters are not valid until they have
been thoroughly checked and saved. Until then, as in the case of invalid parameters, the previous in­
ternal settings apply.
Depending on the parameter, no valid input data may be available for up to max. 30 ms after a value
modification.
Special instructions on avoiding parameterisation errors
In order to avoid parameterisation errors, the sequence described below must be complied with when
modifying the following parameters:
– Units
– Upper limit value x
Example: Parameterisation of pressure
Sequence for first or startup parameterisation (MSE6-E2M in delivery status, monitoring of paramet­
erisation errors active):
1. Set desired unit in "Units" module parameter.
2. Set upper and lower limit values in "Pressure limit values" module parameter.
Sequence for modifying the parameterisation:
1. Deactivate the monitoring for parameterisation errors in the "Monitoring" module parameter.
2. Set parameters ofMSE6-E2M.
• Set the upper limit value in the "Limit values" module parameter to 32767.
• Set desired unit in "Unit Pressure" module parameter.
• Set upper and lower limit values in "Limit values" module parameter if required.
3. Activate the monitoring for parameterisation errors in the "Monitoring" module parameter.
Festo – MSE6-E2M-SY-EN – 1703d – English