Parameters and data
Diagnostic memory parameters: Fault end filter
Function no.
3484
Description
Diagnostic memory filter with which can be used to determine whether running
errors are to be recorded or not.
Bit
Bit 3
Values
Fault end filter
Bit 3
Description
0
Record running errors (end of error) (filter inactive,
presetting)
1
Do not record running errors (fault end) (filter active)
Comment
By recording the running faults it can be determined how long the error has exis­
ted. Incoming and running faults each represent one entry. With running faults,
the error number "0" is entered. A maximum of 40 entries are saved together.
Tab. C.13
Fault end filter
Diagnostic memory parameters: Error number filter
Function no.
3484
Description
With this diagnostic memory filter you can:
– Suppress the recording of a desired error message
– Record exclusively a desired error message.
Bit
Bit 4, 5
Values
Fault numbers filter
FN = Error number
Bit 5
4 Description
0
0
Error number filter inactive (presetting)
0
1
Record only defined FN
1
0
Do not record defined FN
1
1
Reserved
Comment
The error number is determined by means of the diagnostic memory parameter
"Error number" (function no. 3487).
Tab. C.14
Error number filter