C
Parameters and data
Diagnostic memory parameters: Module/channel filter
Function no.
3484
Description
With this diagnostic memory filter, the recording of errors of other modules or
channels can be suppressed so that errors in a particular module or channel can
be analysed.
Bit
Bit 6, 7
Values
Module/channel filter
FN = Error number
Bit 7
6
Description
0
0
Module/channel filter inactive (presetting)
0
1
Record only the FN of a module
1
0
Record only the FN of a channel
1
1
Reserved
Comment
The appropriate numbers are determined by means of the diagnostic memory
parameters "Module number" and "Channel number" (function nos.
3485...3486).
Tab. C.15
Module/channel filter
Diagnostic memory parameters: Module number (MN)
Function no.
3485
Description
Module number for the diagnostic memory filter
Bit
0 ... 7
Values
Module number (MN)
0 ... 47
Comment
Is only effective if an appropriate diagnostic memory filter is active.
Tab. C.16
Module number (MN)
Diagnostic memory parameters: Channel number (CN)
Function no.
3486
Description
Channel number for the diagnostic memory filter
Bit
0 ... 7
Values
Channel number (CN)
0 ... 63
Comment
Is only effective if an appropriate diagnostic memory filter is active.
Tab. C.17
Channel number (CN)
Festo – MSE6-E2M-SY-EN – 1703d – English
(1 byte)
Module number (0 = presetting)
(1 byte)
Channel number (0 = presetting)
[Module/channel filter]
[Inactiv]
[Rec. FN of a mod.]
[Rec, FN of a ch.]
[Module number MN]
[Channel number CN]