8
Diagnostics and error handling
8.2.2
Network-specific LED indicatorsCPX-FB13
[BF] – Bus Failure
LED (red)
Sequence
ON
OFF
flashes
ON
OFF
off
Tab. 8.6 LED indicator [BF] – Bus Failure
8.2.3
Network-specific LED indicators CPX-(M)-FB33/34/35
[NF] – Network Failure
LED (red)
Sequence
ON
OFF
flashes
ON
OFF
off
Tab. 8.7 LED indicator [NF] – Network Failure
Festo – MSE6-E2M-SY-EN – 1703d – English
Significance
Bus connection not OK. Possible
causes:
– Station number not correct
(e.g. address assigned twice)
– Bus interface defective
– Bus connection interrupted
or short-circuited
– Faulty configuration
No error (if the "PS" LED is lit)
Significance
Network connection not OK.
Possible causes:
– Configuration defective (e.g.
MAC-ID not configured)
– Device name or device
number not correct
– IO controller defective
– network connection interrup
ted, short-circuited or dis
turbed
No error (if the "PS" LED is lit)
Remedy
Check address setting of the
DIL switches in the bus node.
Check bus interface of the
master.
Check bus connection.
Check configuration of the
master.
–
Remedy
Check the configuration.
Check device name or device
number.
Repair IO controller.
Check network connection.
–
87