Parameters and data
System data: System start
Function no.
0
Description
Specifies how the system start of the MSE6-E2M is to be carried out.
Bit
Bit 7
Values
System start
Bit 7
Description
0
System start with default parameterisation (factory
setting) and current expansion
1
System start with saved parameterisation and saved
equipment status
è also "System start" system parameter
Comment
Tab. C.38
System start
System data: Fail safe
Function no.
1
Description
Specifies whether Fail safe is active or inactive.
Bit
Bit 0, 1
Values
Fail safe
Bit 1
0
Description
0
0
Reset all outputs
0
1
Hold last state (retain signal status)
1
0
Assume Fault mode
Tab. C.39
Fail safe
Festo – MSE6-E2M-SY-EN – 1703d – English
[System start]
[Default parameters]
[Saved parameters]
[Fail safe]
[Reset outputs]
[Hold last state]
[Assume fault mode]