Commissioning
4.4.4

Setting the DIL switch

Note
The bus node includes electrostatically sensitive devices.
Malfunction or damage to the electronics
• Do not touch any components.
• Observe the handling specifications for electrostatically sensitive devices.
You can set the following parameters with the DIL switches:
– Operating mode (the MSE6-E2M only supports the Remote I/O operating mode in connection with
the bus node CPX-(M)-FB33/34/35)
– Diagnostic mode.
1. Switch off power supply.
2. Unscrew and remove the fastening screws of the cover
3. Remove cover.
è 2 DIL switches appear.
4. Use DIL switch 1 to set operating mode.
5. Set diagnostic mode using DIL switch 2.
6. Fit cover.
7. Tighten mounting screws of the cover at first by hand and then with 0.4 Nm ± 10 %.
1
DIL switch 1: Operating mode
2
DIL switch 2: Diagnostic mode
3
Memory card
Fig. 4.10
DIL switches on bus node CPX-(M)-FB33/34/35
Festo – MSE6-E2M-SY-EN – 1703d – English
.
1
2
3
35