Troubleshooting
Causes of wireless slave station errors and remedies by WS LED
(LEDs with a "*" mark display error occurrence node addresses alternately.)
WS LED
LED display Condition
status
NNODE
ON
WS
E2
(red)
E2
WS
Flashing
(red)
OFF
WS
ON
(red)
OFF
WS
Flashing
(red)

10-2-3 Check by status area and remedy

150
Cause
Unrecoverable error Node address duplication
in wireless zone
Verify error, routing error
Recoverable error
Wireless zone timeout
Unrecoverable error Relay station
Node address duplication
in wireless zone, verify
error, routing error
Unrecoverable error Relay station
Wireless zone timeout
Note Refer to 10-1 Normal Indication for details on the conditions when the WS
LED is green and flashing.
When "Status" is selected in the DIP switch settings of the wireless master
station, the status area that displays the wireless slave station status is avail-
able in the first two or four words of the input area in the Master. The contents
and causes of errors can be found by checking this area.
To be concrete, an error flag is allocated for each wireless station in the status
area, as shown in the following diagram.
1. When maximum number of I/O = 32 words/32 words:
Status begins Wd + 0
Status begins Wd + 1
15 14 13 12 11 10
16 15 14 13 12 11 10
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
2. When maximum number of I/O = 100 words/100 words:
Remedy
Check the switch setting and reset cor-
rectly. If normal operation is not restored,
it is possible that intermodulation is the
cause of the error. With reference to
Points for Consideration with Wireless
Systems on page 16, reset the frequency
to a level for which intermodulation does
not occur.
Check the settings and reset correctly.
Set the unit so the wireless communica-
tion is stabilized by changing the fre-
quency (WCH) or implementing the setup
test.
Check the settings and reset correctly.
Set the unit so the wireless communica-
tion is stabilized by changing the fre-
quency (WCH) or implementing the setup
test.
15
8
7
Slave error flag
9
8
7
6
5
4
9
8
7
6
5
Section 10-2
1
0
3
2
1
0
4
3
2
1