5.7 INPUTS/OUTPUTS
a) DIRECT INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT INPUT
These settings specify how the direct input information is processed. The
assign a descriptive name to the direct input. The
specified direct input is driven by the device identified here.
The
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
The
DIRECT INPUT 1 DEFAULT STATE
5
following choices are available:
Setting
DIRECT INPUT 1 DEFAULT STATE
Setting
DIRECT INPUT 1 DEFAULT STATE
Setting
DIRECT INPUT 1 DEFAULT STATE
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 1. When communication resumes, the input becomes fully operational.
Setting
DIRECT INPUT 1 DEFAULT STATE
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 0. When communication resumes, the input becomes fully operational.
b) DIRECT OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT OUTPUT
The
DIRECT OUT 1 NAME
the FlexLogic™ operand that determines the state of this direct output.
c) APPLICATION EXAMPLES
The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued
below to illustrate usage of the direct inputs and outputs.
5-278

DIRECT INPUTS
1
DIRECT INPUT
NAME: Dir Ip 1
DIRECT INPUT
MESSAGE
DEVICE ID: 1
DIRECT INPUT
MESSAGE
BIT NUMBER:
DIRECT INPUT
MESSAGE
DEFAULT STATE: Off
DIRECT INPUT
MESSAGE
EVENTS: Disabled
is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
. This corresponds to the direct output number of the sending device.
represents the state of the direct input when the associated direct device is offline. The
to "On" value defaults the input to Logic 1.
to "Off" value defaults the input to Logic 0.
to "Latest/On" freezes the input in case of lost communications. If the latest
to "Latest/Off" freezes the input in case of lost communications. If the latest

DIRECT OUTPUTS
1
DIRECT OUT
Dir Out 1
DIRECT OUT
MESSAGE
Off
DIRECT OUTPUT
MESSAGE
EVENTS: Disabled
setting allows the user to assign a descriptive name to the direct output. The
L60 Line Phase Comparison System
DIRECT INPUT 1(32)
Range: up to 12 alphanumeric characters
1
Range: 1 to 16
1
Range: 1 to 32
1
1
Range: On, Off, Latest/On, Latest/Off
1
Range: Enabled, Disabled
1
DIRECT INPUT 1 NAME
represents the source of direct input 1. The
DIRECT INPUT 1 DEVICE ID
DIRECT OUTPUT 1(32)
Range: up to 12 alphanumeric characters
1 NAME:
Range: FlexLogic™ operand
1 OPERAND:
Range: Enabled, Disabled
1
5 SETTINGS

5.7.10 DIRECT INPUTS AND OUTPUTS

setting allows the user to
DIR OUT 1 OPERAND