Before backing up settings and upgrading, set the Settings > Product Setup > Security > Dual Permission Security
Access > Remote Setting Authorized and Local Setting Authorized settings to "ON." Otherwise, the upgrade is blocked
and results in an "Unable to put relay in flash mode" message.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firm-
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
NOTE
The
EEPROM DATA ERROR
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
The EnerVista UR Setup software main window supports the following primary display components:
1.
Title bar which shows the pathname of the active data view.
2.
Main window menu bar.
3.
Main window tool bar.
4.
Site list control bar window.
5.
Settings list control bar window.
6.
Device data view windows, with common tool bar.
7.
Settings file data view windows, with common tool bar.
8.
Workspace area with data view tabs.
9.
Status bar.
10. Quick action hot links.
GE Multilin
4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
message displayed after upgrading/downgrading the firmware is a resettable, self-test
L60 Line Phase Comparison System

4.1.4 ENERVISTA UR SETUP MAIN WINDOW

4
4-3