5.2 PRODUCT SETUP
l) ETHERNET SWITCH
PATH: SETTINGS
PRODUCT SETUP
 ETHERNET SWITCH
These settings appear only if the L60 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The
through
PORT 1 EVENTS
recorder.
5
PATH: SETTINGS
PRODUCT SETUP
 MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
5-38

COMMUNICATIONS
SWITCH IP ADDRESS:
127.0.0.1
SWITCH MODBUS TCP
MESSAGE
PORT NUMBER: 502
PORT 1 EVENTS:
MESSAGE
Disabled
PORT 2 EVENTS:
MESSAGE
Disabled
PORT 6 EVENTS:
MESSAGE
Disabled
settings allow Ethernet switch module events to be logged in the event
PORT 6 EVENTS


MODBUS USER MAP

ADDRESS
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS 256:
MESSAGE
VALUE:
line (this value must be converted from hex to decimal format). The corresponding value is dis-
values can be entered as required in any of the register positions.
ADDRESS
L60 Line Phase Comparison System

ETHERNET SWITCH
Range: standard IP address format
Range: 1 to 65535 in steps of 1
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: 0 to 65535 in steps of 1
1:
0
0
Range: 0 to 65535 in steps of 1
2:
0
0
Range: 0 to 65535 in steps of 1
3:
0
0
Range: 0 to 65535 in steps of 1
0
0
lines automatically returns values for the previous
ADDRESS
5 SETTINGS
5.2.5 MODBUS USER MAP