Managed Switch Led Indicators; Initial Setup Of The Ethernet Switch Module - GE L60 Instruction Manual

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

3 HARDWARE
The wiring for the managed Ethernet switch module is shown below.
Figure 3–48: MANAGED ETHERNET SWITCH MODULE WIRING
The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.
a) DESCRIPTION
Upon initial power up of a L60 device with an installed Ethernet switch, the front panel trouble LED will be illuminated and
the
error message will be displayed. It will be necessary to configure the Ethernet switch and then
ENET MODULE OFFLINE
place it online. This involves two steps:
1.
Configuring the network settings on the local PC.
2.
Configuring the L60 switch module through EnerVista UR Setup.
These procedures are described in the following sections. When the L60 is properly configured, the LED will be off and the
error message will be cleared.
GE Multilin
Connection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)
Link indicator (ON = link active; FLASHING = activity)
Duplex mode indicator (OFF = half-duplex; ON = full-duplex)
Link indicator (ON = link active; FLASHING = activity)
Figure 3–49: ETHERNET SWITCH LED INDICATORS

3.4.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULE

L60 Line Phase Comparison System
3.4 MANAGED ETHERNET SWITCH MODULES

3.4.3 MANAGED SWITCH LED INDICATORS

842868A2.CDR
3
3-47

Advertisement

Table of Contents
loading