Virtual Inputs - GE L60 Instruction Manual

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5.7 INPUTS/OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 VIRTUAL INPUT
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
menu) and communications protocols. All virtual input operands are defaulted to "Off" (logic 0) unless the appropri-
MANDS
ate input signal is received.
If the
VIRTUAL INPUT x FUNCTION
input. If set to "Enabled", the input operates as shown on the logic diagram and generates output FlexLogic™ operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic™ equations and then return
to off. If set to "Latched", the virtual input sets the state of the output operand to the same state as the most recent received
input.
5
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic™ equations. If
the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will likely have to be length-
NOTE
ened in time. A FlexLogic™ timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1
"Virtual Input 1 to ON = 1"
"Virtual Input 1 to OFF = 0"
SETTING
VIRTUAL INPUT 1
TYPE:
Latched
Self - Reset
5-270


VIRTUAL INPUTS

1
VIRTUAL INPUT
FUNCTION: Disabled
VIRTUAL INPUT
MESSAGE
Virt Ip 1
VIRTUAL INPUT
MESSAGE
TYPE: Latched
VIRTUAL INPUT
MESSAGE
EVENTS: Disabled
is to "Disabled", the input will be forced to off (logic 0) regardless of any attempt to alter the
AND
AND
AND
Figure 5–142: VIRTUAL INPUTS SCHEME LOGIC
L60 Line Phase Comparison System
VIRTUAL INPUT 1(64)
Range: Disabled, Enabled
1
Range: Up to 12 alphanumeric characters
1 ID:
Range: Self-Reset, Latched
1
Range: Disabled, Enabled
1
is "Self-Reset", when the input signal tran-
VIRTUAL INPUT x TYPE
S
Latch
R
5 SETTINGS
5.7.2 VIRTUAL INPUTS
COM-
SETTING
VIRTUAL INPUT 1 ID:
(Flexlogic Operand)
OR
Virt Ip 1
827080A2.CDR
GE Multilin

Advertisement

Table of Contents
loading