GE L60 Instruction Manual page 586

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 57)
ADDR
REGISTER NAME
754A
Disconnect Switch 1 Phase A / Three-Pole Opened
754B
Disconnect Switch 1 Phase B Closed
754C
Disconnect Switch 1 Phase B Opened
754D
Disconnect Switch 1 Phase C Closed
754E
Disconnect Switch 1 Phase C Opened
B
754F
Disconnect Switch 1 Operate Time
7550
Disconnect Switch 1 Alarm Delay
7552
Disconnect Switch 1 Events
7553
Reserved (2 items)
7555
...Repeated for Disconnect Switch 2
756A
...Repeated for Disconnect Switch 3
757F
...Repeated for Disconnect Switch 4
7594
...Repeated for Disconnect Switch 5
75A9
...Repeated for Disconnect Switch 6
75BE
...Repeated for Disconnect Switch 7
75D3
...Repeated for Disconnect Switch 8
75E8
...Repeated for Disconnect Switch 9
75FD
...Repeated for Disconnect Switch 10
7612
...Repeated for Disconnect Switch 11
7627
...Repeated for Disconnect Switch 12
763C
...Repeated for Disconnect Switch 13
7651
...Repeated for Disconnect Switch 14
7666
...Repeated for Disconnect Switch 15
767B
...Repeated for Disconnect Switch 16
Thermal Overload Protection (Read/Write Settings) (2 modules)
7738
Thermal Protection 1 Function
7739
Thermal Protection 1 Source
773A
Thermal Protection 1 Base Current
773B
Thermal Protection 1 K Factor
773C
Thermal Protection 1 Trip Time Constant
773D
Thermal Protection 1 Reset Time Constant
773E
Thermal Protection 1 Minimum Reset Time
773F
Thermal Protection 1 Reset
7740
Thermal Protection 1 Block
7741
Thermal Protection 1 Target
7742
Thermal Protection 1 Events
7743
Reserved (2 items)
7745
Repeated for Thermal Protection 2
Ohm Inputs (Read/Write Setting) (2 modules)
7840
Ohm Inputs 1 Function
7841
Ohm Inputs 1 ID
7847
Ohm Inputs 1 Reserved (9 items)
7850
...Repeated for Ohm Inputs 2
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
7B61
User Programmable Pushbutton 1 Top Line
7B6B
User Programmable Pushbutton 1 On Text
7B75
User Programmable Pushbutton 1 Off Text
7B7F
User Programmable Pushbutton 1 Drop-Out Time
7B80
User Programmable Pushbutton 1 Target
7B81
User Programmable Pushbutton 1 Events
7B82
User Programmable Pushbutton 1 LED Operand
7B83
User Programmable Pushbutton 1 Autoreset Delay
7B84
User Programmable Pushbutton 1 Autoreset Function
B-38
RANGE
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65.535
0 to 65.535
0 to 1
---
0 to 1
0 to 5
0.2 to 3
1 to 1.2
0 to 1000
0 to 1000
0 to 1000
0 to 65535
0 to 65535
0 to 2
0 to 1
---
0 to 1
---
0 to 65535
0 to 2
---
---
---
0 to 60
0 to 2
0 to 1
0 to 65535
0.2 to 600
0 to 1
L60 Line Phase Comparison System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
F001
---
1
F102
---
1
F167
pu
0.01
F001
---
0.05
F001
min.
1
F001
min.
1
F001
min.
1
F001
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
---
F205
---
1
F001
---
1
F137
---
---
F202
---
---
F202
---
---
F202
s
0.05
F001
---
1
F109
---
1
F102
---
1
F300
s
0.1
F001
---
1
F102
DEFAULT
0
0
0
0
0
70
0
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
80
110
45
45
20
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"Ohm Ip 1 "
0
0 (Disabled)
(none)
(none)
(none)
0
0 (Self-reset)
0 (Disabled)
0
10
0 (Disabled)
GE Multilin