Advertisement

5 SETTINGS
The
setting specifies the operating threshold for the effective operating signal of the element. If set
FLEXELEMENT 1 PICKUP
to "Over", the element picks up when the operating signal exceeds the
element picks up when the operating signal falls below the
The
FLEXELEMENT 1 HYSTERESIS
and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexEle-
ment™ can be programmed to work with all analog actual values measured by the relay. The
ting is entered in per-unit values using the following definitions of the base units:
Table 5–13: FLEXELEMENT™ BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FAULT LOCATION
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
GE Multilin
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
Figure 5–43: FLEXELEMENT™ INPUT MODE SETTING
FLEXELEMENT 1 PICKUP
setting controls the element dropout. It should be noticed that both the operating signal
2
× cycle
BASE = 2000 kA
BASE = maximum value of the
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
L60 Line Phase Comparison System
FLEXELEMENT 1 PKP
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FlexElement 1 OpSig
842706A2.CDR
FLEXELEMENT 1 PICKUP
value.
setting for the two transducers configured
DCMA INPUT MAX
5.4 FLEXLOGIC™
value. If set to "Under", the
set-
FLEXELEMENT 1 PICKUP
5-109
5