Irig-B - GE L60 Instruction Manual

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

3.2 WIRING
3 HARDWARE

3.2.9 IRIG-B

IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The
IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the L60 operates an internal oscillator with 1
µs resolution and accuracy. The IRIG time code formats are serial, width-modulated codes which can be either DC level
shifted or amplitude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment
may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be
synchronized.
3
Figure 3–24: OPTIONS FOR IRIG-B CONNECTION
3-24
L60 Line Phase Comparison System
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents