GE L60 Instruction Manual page 251

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
a) MAIN MENU

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE COMPARISON
 ELEMENTS
MESSAGE
MESSAGE
MESSAGE
b) 87PC SCHEME

PATH: SETTINGS
GROUPED ELEMENTS
 87PC SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
PHASE COMPARISON ELEMENTS
 87PC SCHEME
 ADVANCED
 FAULT DETECTORS
 CHARGE CURRENT
 COMPENSATION
 OPEN BREAKER
 ECHO
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
87PC FUNCTION:
Disabled
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
87PC BLOCK:
Off
87PC SIGNAL SOURCE:
One Source Current
87PC SIGNAL:
Mixed I_2-K*I_1
87PC MIXED SIGNAL K:
0.20
87PC MIXED SIGNAL
REF ANGLE: 0°
87PC FDL PICKUP:
0.50 pu
87PC FDL AUX:
Off
87PC FDH PICKUP:
0.75 pu
87PC FDH AUX:
Off
87PC FDH SUPV:
Off
87PC CH1 ASYMMETRY:
0.0 ms
87PC CH2 ASYMMETRY:
0.0 ms
87PC CH1 DELAY:
0.0 ms
L60 Line Phase Comparison System
5.5 GROUPED ELEMENTS
5.5.3 PHASE COMPARISON ELEMENTS
See page 5–113.
See page 5–121.
See page 5–128.
See page 5–130.
87PC SCHEME
Range: Disabled, Enabled
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
Range: FlexLogic™ operand
Range: One Source Current, Two Sources Current
Range: Mixed I_2–K*I_1, Mixed I_1+I_2/K, 3I_0
Range: 0.00 to 0.25 in steps of 0.01
Range: 0 to 359° in steps of 1
Range: 0.02 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: 0.05 to 15.00 pu in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: –5.0 to 5.0 ms in steps of 0.1
Range: –5.0 to 5.0 ms in steps of 0.1
Range: 0.0 to 30.0 ms in steps of 0.1
5
5-113