APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 41 of 57)
ADDR
REGISTER NAME
AEF5
Repeated for IEC 61850 XSWI20
AEF7
Repeated for IEC 61850 XSWI21
AEF9
Repeated for IEC 61850 XSWI22
AEFB
Repeated for IEC 61850 XSWI23
AEFD
Repeated for IEC 61850 XSWI24
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write Setting)
AF00
Number of Analog Input Points in GGIO4
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules)
AF10
IEC 61850 GGIO4 Analog Input 1 Value
AF11
IEC 61850 GGIO4 Analog Input 1 Deadband
AF13
IEC 61850 GGIO4 Analog Input 1 Minimum
AF15
IEC 61850 GGIO4 Analog Input 1 Maximum
AF17
...Repeated for IEC 61850 GGIO4 Analog Input 2
AF1E
...Repeated for IEC 61850 GGIO4 Analog Input 3
AF25
...Repeated for IEC 61850 GGIO4 Analog Input 4
AF2C
...Repeated for IEC 61850 GGIO4 Analog Input 5
AF33
...Repeated for IEC 61850 GGIO4 Analog Input 6
AF3A
...Repeated for IEC 61850 GGIO4 Analog Input 7
AF41
...Repeated for IEC 61850 GGIO4 Analog Input 8
AF48
...Repeated for IEC 61850 GGIO4 Analog Input 9
AF4F
...Repeated for IEC 61850 GGIO4 Analog Input 10
AF56
...Repeated for IEC 61850 GGIO4 Analog Input 11
AF5D
...Repeated for IEC 61850 GGIO4 Analog Input 12
AF64
...Repeated for IEC 61850 GGIO4 Analog Input 13
AF6B
...Repeated for IEC 61850 GGIO4 Analog Input 14
AF72
...Repeated for IEC 61850 GGIO4 Analog Input 15
AF79
...Repeated for IEC 61850 GGIO4 Analog Input 16
AF80
...Repeated for IEC 61850 GGIO4 Analog Input 17
AF87
...Repeated for IEC 61850 GGIO4 Analog Input 18
AF8E
...Repeated for IEC 61850 GGIO4 Analog Input 19
AF95
...Repeated for IEC 61850 GGIO4 Analog Input 20
AF9C
...Repeated for IEC 61850 GGIO4 Analog Input 21
AFA3
...Repeated for IEC 61850 GGIO4 Analog Input 22
AFAA
...Repeated for IEC 61850 GGIO4 Analog Input 23
AFB1
...Repeated for IEC 61850 GGIO4 Analog Input 24
AFB8
...Repeated for IEC 61850 GGIO4 Analog Input 25
AFBF
...Repeated for IEC 61850 GGIO4 Analog Input 26
AFC6
...Repeated for IEC 61850 GGIO4 Analog Input 27
AFCD
...Repeated for IEC 61850 GGIO4 Analog Input 28
AFD4
...Repeated for IEC 61850 GGIO4 Analog Input 29
AFDB
...Repeated for IEC 61850 GGIO4 Analog Input 30
AFE2
...Repeated for IEC 61850 GGIO4 Analog Input 31
AFE9
...Repeated for IEC 61850 GGIO4 Analog Input 32
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
B01D
IEC 61850 GSSE Function (GsEna)
B01E
IEC 61850 GSSE ID
B03F
IEC 61850 GOOSE Function (GoEna)
B040
IEC 61850 GSSE Destination MAC Address
B043
IEC 61850 Standard GOOSE ID
B064
IEC 61850 Standard GOOSE Destination MAC Address
B067
IEC 61850 GOOSE VLAN Transmit Priority
B068
IEC 61850 GOOSE VLAN ID
GE Multilin
RANGE
4 to 32
---
0.001 to 100
–1000000000000 to
1000000000000
–1000000000000 to
1000000000000
1 to 60
0 to 1
---
0 to 1
---
---
---
0 to 7
0 to 4095
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
4
F001
---
---
F600
%
0.001
F003
---
0.001
F060
---
0.001
F060
s
1
F001
---
1
F102
---
---
F209
---
1
F102
---
---
F072
---
---
F209
---
---
F072
---
1
F001
---
1
F001
DEFAULT
B
4
0
100000
0
1000000
60
1 (Enabled)
"GSSEOut"
0 (Disabled)
0
"GOOSEOut"
0
4
0
B-49